SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
4.9 Verifying Parameter Settings and Backing Up Changes
4.9 Verifying Parameter Settings and Backing Up Changes
Check changes to parameter settings as a result of Auto-Tuning using the Verify function.
Changes: Verify Menu on page 82
Save the verified parameter settings. Change the access level or set a password to the drive to prevent accidental
modification of parameter settings.
◆
Backing Up Parameter Values: o2-03
Performing the following procedure stores all parameters settings to drive memory where they can later be recalled if
necessary. Set o2-03 to “1” to save parameter changes. This saves all parameter settings, and then returns o2-03 to 0. The
drive can now “recall” the saved parameters by performing a “user-initialization” (A1-03 = 1110).
◆
Parameter Access Level: A1-01
Setting the Access Level for “Operation only” (A1-01 = 0) allows the user to access parameters A1-
and U
-
only. Other parameters are not displayed.
Setting the Access Level for “User Parameters” (A1-01 = 1) allows the user to access parameters that have been
previously saved as User Parameters. This is helpful when displaying only the relevant parameters for a specific
application.
No.
Parameter
Name
Description
Setting
Range
Default
Setting
o2-03
User Parameter
Default Value
Allows storing of parameter settings as a User Initialization Selection.
0: Saved/Not set
1: Set Defaults - Saves current parameter settings as user default settings.
2: Clear All - Clears the currently saved user settings. After saving the user parameter
set value, the items of 1110 (User Parameter Initialize) are displayed in A1-03 (User
Parameter Default Value).
0 to 2
0
A1-03
Initialize
Parameters
Selects a method to initialize the parameters.
0: No Initialize
1110: User Initialize (The user must first program and store desired settings using
parameter o2-03)
2220: 2-Wire Initialization (parameter initialized prior to shipment)
3330: 3-Wire Initialization
5550: oPE4 Fault reset
0 to 5550
0
No.
Parameter
Name
Description
Setting
Range
Default
A1-01
Access Level
Selection
Selects which parameters are accessible via the digital operator.
0: Operation only (A1-01 and -04 can be set and monitored. U parameters can be monitored)
1: User Parameters (Only those recently changed among application parameters A2-01 to A2-
16 and A2-17 to A2-32 can be set and monitored)
2: Advanced Access Level (All parameters can be set and monitored)
0 to 2
2
A2-01
to
A2-32
User
Parameters 1
to 32
Parameters selected by the user are stored to the User Parameter menu. This includes recently
viewed parameters or parameters specifically selected for quick access.
If parameter A2-33 is set to 1, recently viewed parameters will be listed between A2-17 and
A2-32. Parameters A2-01 through A2-16 must be manually selected by the user.
If A2-33 is set to 0, then recently viewed parameters will not be saved to the User Parameter
group. The entire A2 parameter group is now available for manual programming.
b1-01 to
o2-08
–
A2-33
User
Parameter
Automatic
Selection
0: Parameters A2-01 through A2-32 are reserved for the user to create a list of User
Parameters.
1: Save history of recently viewed parameters. Recently edited parameters will be saved to
A2-17 through A2-32 for quick access. The most recently changed parameter is registered in
A2-17. The second most recently changed parameter is registered in A2-18.
0, 1
1
Содержание T1000V
Страница 10: ...10 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 30: ...1 4 Component Names 30 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 44: ...2 2 Mechanical Installation 44 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 100: ...4 10 Test Run Checklist 100 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 232: ...5 12 U Monitor Parameters 232 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 280: ...6 9 Troubleshooting without Fault Display 280 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 294: ...7 5 Drive Replacement 294 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 306: ...8 5 Communication Options 306 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 316: ...A 6 Drive Derating Data 316 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 422: ...D 4 Safe Disable Input Precautions 422 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...