A.4 Drive Specifications
YASKAWA ELECTRIC
SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
311
S
p
ec
if
ic
at
ions
A
A.4 Drive Specifications
Note:
Perform rotational Auto-Tuning to obtain OLV performance specifications.
Note:
For optimum performance life of the drive, install the drive in an environment that meets the environmental conditions.
Item
Specification
Control
Characteristics
Control Method
The following control methods are available:
Open Loop Vector Control (current vector), V/f Control, and PM Open Loop Vector for
(for use with SPM and IPM)
Frequency Control Range
0.01 to 400 Hz
Frequency Accuracy
Digital input: within ±0.01% of the max output frequency (-10 to +50 °C)
Analog input: within ±0.5% of the max output frequency (25 °C ±10 °C)
Frequency Setting Resolution
Digital inputs: 0.01 Hz
Analog inputs: 1/1000 of maximum output frequency
Output Frequency Calculation
Resolution
1/2
20
x Maximum output frequency (E1–04)
Frequency Setting Signal
Main frequency reference: 0 to +10 Vdc (20 k
Ω
), 4 to 20 mA (250
Ω
), 0 to 20 mA
(250
Ω
)
Main speed reference: Pulse Train Input (max 32 kHz)
Starting Torque
200%/0.5 Hz (Open Loop Vector Control, HD rating, IM of 4.0 kW or smaller), 50%/6
Hz (PM Open Loop Vector Control)
Speed Control Range
1:100 (Open Loop Vector Control), 1:40 (V/f Control), 1:10 (PM Open Loop Vector
Control)
Speed Control Accuracy
±0.2% in Open Loop Vector Control
Speed Response
5 Hz (25 °C ±10 °C) in Open Loop Vector Control
(excludes temperature fluctuation when performing Rotational Auto-Tuning)
Torque Limit
Open Loop Vector Control only. Adjustable in 4 quadrants.
Accel/Decel Time
0.00 to 6000.0 s (allows four separate settings for accel and decel)
Braking Torque
Instantaneous Average Decel Torque
: 0.1/0.2 kW: over 150%, 0.4/0.75 kW: over
100%, 1.5 kW: over 50%, 2.2 kW and above: over 20%
Continuous Regen Torque: 20%,
125% with a Braking Resistor Unit
: (10% ED) 10 s with an internal braking resistor.
V/f Characteristics
User-set program available.
Functions
Momentary Power Loss Ride-Thru
Speed Search
Over/Undertorque Detection
Torque Limit, Multi-Step Speed (9 steps max)
Accel/Decel Time Switch
S-Curve Accel/Decel
3-Wire Sequence
Rotational Auto-Tuning
Stationary Auto-Tuning of Line-to-Line Resistance
Dwell
Cooling Fan ON/OFF
Slip Compensation
Torque Compensation
Frequency Reference Upper/Lower Limit
DC Injection Braking (start and stop)
PID Control (with Sleep Function)
Energy Saving
MEMOBUS/Modbus (RS-485/422 Max 115.2 kbps)
Fault Reset
Parameter Copy
Disturb Function
Содержание T1000V
Страница 10: ...10 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 30: ...1 4 Component Names 30 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 44: ...2 2 Mechanical Installation 44 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 100: ...4 10 Test Run Checklist 100 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 232: ...5 12 U Monitor Parameters 232 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 280: ...6 9 Troubleshooting without Fault Display 280 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 294: ...7 5 Drive Replacement 294 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 306: ...8 5 Communication Options 306 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 316: ...A 6 Drive Derating Data 316 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 422: ...D 4 Safe Disable Input Precautions 422 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...