3.3.2
Bottom Conduit Entry
All conduit entries must pass through the designated area in the bottom of the inverter. Be sure to remove all
metal chips from the inverter after drilling to prevent metal chips and other debris from potentially damaging the
inverter.
Conduits entering the inverter often allow condensation to form inside the inverter
enclosure. Use an appropriately rated sealant for these conduits to prevent
condensation. Condensation inside the inverter may cause irreparable damage and is
not covered under warranty.
Figure 3-9 Conduit Entry Area
17.32 in. (440mm)
5.51 in. (140mm)
1.38 in. (35mm)
1.18 in.
(30mm)