No.
Parameter Name
Default Setting
E1-03
V/f Pattern Selection
0FH
L2-01
Momentary Power Loss Operation Selection 1: Enabled
L3-04
Stall Prevention Selection during
Deceleration
1: Enabled
Table 4.12 Compressor: User Parameters (A2-01 to A2-16):
No.
Parameter Name
No.
Parameter Name
b1-01
Frequency Reference Selection 1
E1-03 V/f Pattern Selection
b1-02
Run Command Selection 1
E1-07 Middle Output Frequency
b1-04
Reverse Operation Selection
E1-08 Middle Output Frequency Voltage
C1-01 Acceleration Time 1
E2-01 Motor Rated Current
C1-02 Deceleration Time 1
−
−
u
Setting 6: Preset 6
Note:
1.
Read the instructions listed in
Notes on Controlling the Brake when Using Application Preset 6
on
page
when using Application Preset 6
2.
Perform Auto-Tuning after selecting Application Preset 6.
3.
If UL3 appears on the operator display after Auto-Tuning is complete, set L6-01 to “0” to repeat the
Auto-Tuning process.
Table 4.13 Preset 6: Parameters and Settings
No.
Parameter Name
Default Setting
A1-02
Control Method Selection
2: Open Loop Vector Control
b1-01
Frequency Reference Selection 1
0: Operator
b6-01
Dwell Reference at Start
3.0 Hz
b6-02
Dwell Time at Start
0.3 s
C1-01
Acceleration Time 1
3.0 s
C1-02
Deceleration Time 1
3.0 s
C6-01
Drive Duty Selection
0: Heavy Duty
C6-02
Carrier Frequency Selection
2: 5 kHz
d1-01
Frequency Reference 1
6.0 Hz
d1-02
Frequency Reference 2
30.0 Hz
d1-03
Frequency Reference 3
60.0 Hz
E1-03
V/f Pattern Selection
0FH
H2-02
Terminals P1 Function Selection
37: During Frequency Output
4.5 Application Selection
100
YASKAWA ELECTRIC TOEP C710606 47A YASKAWA AC Drive – V1000 Quick Start Guide