n
Setup Group Parameters
lists the parameters available by default in the Setup Group. Selecting an Application Preset in through initialization
in parameter A1-03 automatically changes the parameters selected for the Setup Group.
Refer to Application Selection on
for details on parameters and default values for the fan and pump Setup Groups.
No.
Parameter Name
Setting Range
Default
A1-03
Initialize Parameters
0, 1110, 2220, 3330, 5550,
8008, 8009, 8010, 8011
0
Setting 0: No initialization (default)
Setting 1110: User Initialize (parameter values must be stored using parameter o2-03)
Setting 2220: 2-Wire Initialize
Setting 3330: 3-Wire Initialize
Setting 5550: Terminal/Control Initialize
Setting 8008: Pump
Setting 8009: Pump w/ PI
Setting 8010: Fan
Setting 8011: Fan w/ PI
Use the Programming Mode to access parameters not displayed in the Setup Group.
Table 4.6 General Purpose Application Setup Group Parameters (A1-03 = 0)
Parameter
Name
A1-06
Application Preset Selection (Monitor only)
b1-01
Frequency Reference Selection 1
b1-02
Run Command Selection 1
b1-03
Stopping Method Selection
b1-04
Reverse Operation Selection
C1-01
Acceleration Time 1
C1-02
Deceleration Time 1
d1-01
Frequency Reference 1
d2-01
Frequency Reference Upper Limit
d2-02
Frequency Reference Lower Limit
Parameter
Name
E2-01
Motor Rated Current
L2-01
Momentary Power Loss Operation Selection
L5-01
Number of Auto Restart Attempts
L6-01
Torque Detection 1 Selection
L6-02
Torque Detection 1 Level
L6-03
Torque Detection 1 Time
o1-06
User Monitor Selection Mode
o1-07
Second Line Monitor Selection
o1-08
Third Line Monitor Selection
u
Switching Between LOCAL and REMOTE
LOCAL mode is when the drive is set to accept the Run command from the digital operator RUN key. REMOTE mode is
when the drive is set to accept the Run command from an external device (i.e., input terminals or serial communications).
WARNING! Sudden Movement Hazard. The drive may start unexpectedly if the Run command is already applied when switching from
LOCAL mode to REMOTE mode when b1-07 = 1, resulting in death or serious injury. Be sure all personnel are clear of rotating machinery.
Switch the operation between LOCAL and REMOTE using the LO/RE key on the digital operator or via a digital input.
Note:
1.
After selecting LOCAL, the LO/RE light will remain lit.
2.
The drive will not allow the user to switch between LOCAL and REMOTE during run.
4.3 The Drive, Programming, and Clock Adjustment Modes
122
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Содержание P1000
Страница 4: ...This Page Intentionally Blank 4 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 26: ...i 2 General Safety This Page Intentionally Blank 26 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 140: ...4 11 Test Run Checklist This Page Intentionally Blank 140 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 430: ...A 4 Drive Derating Data This Page Intentionally Blank 430 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 504: ...B 16 Defaults by Drive Model This Page Intentionally Blank 504 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 568: ...D 3 UL and CSA Standards This Page Intentionally Blank 568 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 591: ...Index This Page Intentionally Blank YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual 591...
Страница 593: ......