8 Switches
8
Switches
The CPU Module has the following two types of switches.
• DIP switches: Mode switches
• STOP/SAVE switch
DIP Switches: Mode Switches
The SW1 and SW2 switches are checked at start-up, and their behavior is described in the following tables:
Table 3 SW1 Switches
Table 4 SW2 Switches
E-INIT and - switches can override the Ethernet configuration according to
Table 5
.
Table 5 Operation of E-INIT, E-PM0 and E-PM1 for Configuring Ethernet
On start-up, the controller will automatically load firmware or user projects based on the LOAD and MNT switches. The
USB thumb drive is available in any other circumstances.
Table 6 Operation of LOAD and MNT for USB Thumb Drive
SW
Description
STOP
When ON, prevents PLC from running.
E-INIT
When ON, overrides Ethernet configuration according to
Table 5
.
INIT
When ON, the controller uses the fixed, default configuration
CNFG
When ON, the controller creates Axes and I/O for all connected devices. (Auto-configuration)
SW
Description
LOAD
When ON, load either the user project or firmware from the USB thumb drive. See
Table 6
for details.
TEST
When ON, the IP address is scrolled across the seven segment display.
MNT
When ON, controller starts up in supervisor mode. In this mode MECHATROLINK III, PLC, Modbus/TCP and Ethernet/IP
do not start. The controller firmware can be updated, and clearing DOS FS alarms will repair the DOS FS.
-- / DHCP
DHCP Selection when E-INIT is ON.
E-INIT
-- / DHCP
Static Configuration
OFF
N/A
192.168.1.1
ON
OFF
DHCP
ON
ON
E-INIT
-- / DHCP
Load user project from USB thumb drive
ON
OFF
Install firmware and user project from USB
thumb drive
ON
ON