6 Electrical Installation
YASKAWA ELECTRIC
TOBP C720600 01E YASKAWA AC Drive Option CDBR-
D, LKEB-
Installation Manual
53
Note:
Use the recommended gauges to connect the CDBR Braking Unit to the following drives and to
comply with an IP20 enclosure. The wiring cover for the +3 and - drive terminal must be cut out.
Refer to the drive manual for details.
Drive models: CIPR-GA70
2257 to 2415, 4208 to 4675, CIPR-CH70
2215 to 2415, 4180 to
4605, CIPR-CR70
2215 to 2415, 4180 to 4605
Replacing Previous Version CDBR Braking Unit Models
The terminal size and location are different on CDBR-X, CDBR-XB, or CDBR-XC model
CDBR Braking Units.
Refer to
to ensure proper wiring when replacing an older model CDBR Braking
Unit.
Table 11 CDBR Main Circuit Terminal Cross-Reference Chart
■
Using CDBR Braking Units in Parallel
Install multiple CDBR Braking Units in a master/slave configuration with a single CDBR
Braking Unit as the master as shown in
.
NOTICE:
Perform all wiring and installation as instructed in
. Failure to follow specifications may
damage the drive and the CDBR braking unit.
• Set the Master/Slave Selection Switch (S2) to “Master (OUT)” on one CDBR Braking
Unit only. Set all other CDBR Braking Units to “Slave (IN)”. Refer to
Selection Switch (S2) on page 57
• Select the appropriate CDBR Braking Unit wire types and gauges from
.
• Use shielded twisted-pair cables and keep the wiring distance between the OUT1-IN1 and
OUT2-IN2 terminals of the CDBR Braking Unit shorter than 1 meter (3.28 ft).
<2> Use a gauge that is within the applicable range for gauges for the drive when terminals P and B are connected to
the following drives. Junction terminals are needed to connect to the drives if using a gauge that is smaller than the
applicable range for gauges for the drives. Contact Yaskawa or your nearest sales representative when selecting
and connecting junction terminals.
Drive models: CIPR-GA70
2110, 2138, 4103, CIPR-CH70
2088, 2115, 4091, CIPR-CR70
2088, 2115, 4091
<3> Junction terminals are needed to connect to the drives when terminals P and B are connected to the following
drives. Contact Yaskawa or your nearest sales representative when selecting and connecting junction terminals.
Drive models: CIPR-GA70
4140, 4168, CIPR-CH70
4112, 4150, CIPR-CR70
4112, 4150
CDBR-
D
CDBR-
B, CDBR-
C
CDBR-
-
-
N
+
+
P
B1
+
0
P
0
B2
-
0
B
TOBP_C720600_01E_9_0_E_chap1-10.fm 53 ページ 2017年9月1日 金曜日 午前9時33分