3006: General HOA Keys
x
AUTO Run = AUTO key + S1,
Speed = A2
HAND1 Run = S6,
Speed = P5-02
or Operator when P5-01 = 1,
otherwise Terminal A1
HAND2 Run = S7,
Speed = P5-05 or Operator
Run
Fault
Reset
HAND1
HAND2
Comms Run
Drive
Serial Comms
AUTO Speed Ref
Def: 4 to 20 mA (H3-09)
P5-01 = 0
HAND1 Speed Ref
Def: 0 to 10 V (H3-01)
Ext. Pump
Fault (N.O.)
Ext. Pump
Fault (N.O.)
Ext. Pump
Fault (N.O.)
S1
S2
S3
S4
S5
S6
S7
S8
SN
24V
+V
A1
A2
A3
AC
R+
R- S+ S-
Switch to Net Coms = S8;
AUTO Run = Auto key + Serial Run,
Speed = Serial Comms
Figure 4.32 Default Port Configuration for General HOA Keys
n
b1-01: Frequency Reference Selection 1
Selects the frequency reference source 1 for the REMOTE mode.
Note:
If a Run command is input to the drive but the frequency reference entered is 0 or below the minimum frequency, the RUN indicator LED
on the digital operator will light and the STOP indicator will flash.
No.
Parameter Name
Setting Range
Default
b1-01
Frequency Reference Selection 1
0 to 5
0
In order to run the drive and motor, the drive must receive a Run command and an Auto Setpoint command. Parameter b1-01
specifies the origin of the Auto setpoint when in AUTO Mode. Switch to AUTO mode by pressing the AUTO button on the
HOA keypad while the drive is stopped.
Note:
If a Run command is input to the drive without a corresponding Auto setpoint, the Run indicator on the HOA keypad will turn on and the
STOP indicator on the keypad will blink.
If the drive should follow the “HAND Reference” set by the HOA keypad, use HAND Mode by pressing the HAND key and
set P5-01 to “1: Hand Reference (P5-02).” The HAND reference can then be entered into the U1-01 monitor parameter in the
“-DRIVE- ” Menu.
The drive offers the ability to provide four types of “Auto Setpoint” reference sources. These Auto Setpoint reference sources
are determined by the setting of b1-01 and the drive set to AUTO Mode by pressing the AUTO key on the keypad.
Prior to programming, it is recommended to select the system units (P1-02) and the feedback device, Scaling (P1- 03) first.
P1-03 will automatically scale the drive setpoint.
Example: P1-02 = 1: PSI
P1-03 = 200, feedback range = 200 PSI.
4.7 Basic iQpump Setup and Application Preset Parameters
214
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Содержание iQpump1000
Страница 2: ......
Страница 12: ...This Page Intentionally Blank 12 YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive iQpump1000 User Manual...
Страница 308: ...6 3 Drive Replacement This Page Intentionally Blank 308 YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive iQpump1000 User Manual...
Страница 448: ...B 16 U Monitors This Page Intentionally Blank 448 YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive iQpump1000 User Manual...
Страница 486: ...C 12 Self Diagnostics This Page Intentionally Blank 486 YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive iQpump1000 User Manual...
Страница 507: ......