188 and 1A8: Inverse Inputs of 88 and A8
Setting Value
Function
Description
188 and 1A8
Inverse Inputs of 88 and A8
Sets the function of the selected MFDI to operate inversely. To select the function for inverse input, enter two digits of 88 or A8 for
the
“
xx
”
in
”
1xx
”
.
For example, to use the inverse input of
88 [Thermostat Fault]
, set
H1-xx = 188
.
◆
H2: Digital Outputs
H2 parameters
set the MFDO terminal functions.
■
H2-01 to H2-03 Terminal M1-M2, M3-M4, M5-M6 Function Selection
The drive has three MFDO terminals.
shows the default function settings for the terminals.
Table 5.39 MFDO Terminals Default Function Settings
No.
Name
Default
Function
H2-01
Term M1-M2 Function Selection
0
During Run
H2-02
Term M3-M4 Function Selection
1
Zero Speed
H2-03
Term M5-M6 Function Selection
2
Speed Agree 1
Refer to
to set
H2-xx [MFDO Function Selection]
.
Table 5.40 MFDO Setting Value
Setting Value
Function
Reference
0
During Run
1
Zero Speed
2
Speed Agree 1
3
User-Set Speed Agree 1
4
Frequency Detection 1
5
Frequency Detection 2
6
Drive ready
7
DC Bus Undervoltage
8
During Baseblock (N.O.)
9
Frequency Reference from Keypad
B
Torque Detection 1 (N.O.)
C
Frequency Reference Loss
E
Fault
F
Not Used
10
Alarm
11
Fault Reset Command Active
12
Timer Output
13
Speed Agree 2
14
User-Set Speed Agree 2
15
Frequency Detection 3
16
Frequency Detection 4
17
Torque Detection 1 (N.C.)
18
Torque Detection 2 (N.O.)
19
Torque Detection 2 (N.C.)
1A
During reverse
Setting Value
Function
Reference
1B
During Baseblock (N.C.)
1E
Executing Auto-Restart
1F
Motor Overload Alarm (oL1)
20
Drive Overheat Pre-Alarm (oH)
21
Safe Torque OFF
2F
Maintenance Notification
37
During Frequency Output
38
Drive Enabled
39
Watt Hour Pulse Output
3A
Drive Overheat Alarm
3D
During Speed Search
42
Pressure Reached
4C
During Fast Stop
4D
oH Pre-Alarm Reduction Limit
51
Sequence Timer 1
52
Sequence Timer 2
53
Sequence Timer 3
54
Sequence Timer 4
58
UL6 Underload Detected
60
Internal Cooling Fan Failure
62
Modbus Reg 1 Status Satisfied
63
Modbus Reg 2 Status Satisfied
69
External Power 24V Supply
6A
Data Logger Error
71
Low PI2 Control Feedback Level
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...