SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
OFF : The output frequency < “
L4-03
-
L4-04
”, or the output frequency
≤
L4-03
.
L4-03: Speed Agree Detection Level(+/-)
L4-04: Speed Agree Detection Width(+/-)
Figure 5.55 Example of Frequency Detection 4 (Value of L4-03 is Positive)
■
17: Torque Detection 1 (N.C.)
Setting Value
Function
Description
17
Torque Detection 1 (N.C.)
The terminal deactivates when the drive detects overtorque or undertorque.
Use the
L6 [Torque Detection]
parameters to set torque detection.
OFF : The output current/torque >
L6-02 [Torque Detection Level 1]
, or the output current/torque <
L6-02
for longer than the time set in
L6-03 [Torque Detection Time 1]
.
Note:
•
When
L6-01 ≥ 5
, the drive will detect when the output current/torque is less than
L6-02
for longer than
L6-03
.
•
Refer to
L6: Torque Detection on page 336
for more information.
■
18: Torque Detection 2 (N.O.)
Setting Value
Function
Description
18
Torque Detection 2 (N.O.)
The terminal activates when the drive detects overtorque or undertorque.
Use the
L6 [Torque Detection]
parameters to set torque detection.
ON : The output current/torque >
L6-05 [Torque Detection Level 2]
, or the output current/torque <
L6-
05
for longer than the time set in
L6-06 [Torque Detection Time 2]
.
Note:
•
When
L6-04 ≥ 5
, the drive will detect when the output current/torque is less than
L6-05
for longer than
L6-06
.
•
Refer to
L6: Torque Detection on page 336
for more information.
■
19: Torque Detection 2 (N.C.)
Setting Value
Function
Description
19
Torque Detection 2 (N.C.)
The terminal deactivates when the drive detects overtorque or undertorque.
Use the
L6 [Torque Detection]
parameters to set torque detection.
OFF : The output current/torque >
L6-05 [Torque Detection Level 2]
, or the output current/torque <
L6-05
for longer than the time set in
L6-06 [Torque Detection Time 2]
.
Note:
•
When
L6-04 ≥ 5
, the drive will detect when the output current/torque is less than
L6-05
for longer than
L6-06
.
•
Refer to
L6: Torque Detection on page 336
for more information.
■
1A: During Reverse
Setting Value
Function
Description
1A
During Reverse
The terminal activates when the motor operates in the reverse direction.
ON : The motor is operating in the reverse direction.
OFF : The motor is operating in the forward direction or the motor stopped.
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...