148
YASKAWA
TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
Code
Name
Causes
Possible Solutions
Er-02
Drive in an Alarm State
The motor nameplate data entered during Auto-
Tuning is incorrect.
•
Make sure that the motor nameplate data entered in Auto-Tuning
is correct.
•
Do Auto-Tuning again and correctly set the motor nameplate
data.
You did Auto-Tuning while the drive had a minor
fault or alarm.
Clear the minor fault or alarm and do Auto-Tuning again.
There is a defective motor cable or cable connection.
Examine and repair motor wiring.
The load is too large.
•
Decrease the load.
•
Examine the machine area to see if, for example, the motor shaft
is locked.
The drive detected a minor fault during Auto-Tuning.
1.
Stop Auto-Tuning.
2.
Examine the minor fault code and remove the cause of the
problem.
3.
Do Auto-Tuning again.
Code
Name
Causes
Possible Solutions
Er-03
OFF Button was Pressed
You pushed
during Auto-Tuning.
Auto-Tuning did not complete correctly. Do Auto-Tuning again.
Code
Name
Causes
Possible Solutions
Er-04
Line-to-Line Resistance Error
The Auto-Tuning results were not in the applicable
parameter setting range.
Auto-Tuning did not complete in a pre-set length of
time.
There is a defective motor cable or cable connection.
•
Examine and repair motor wiring.
•
Disconnect the machine from the motor and do Rotational Auto-
Tuning again.
The motor nameplate data entered during Auto-
Tuning is incorrect.
•
Make sure that the input motor nameplate data is correct.
•
Do Auto-Tuning again and correctly set the motor nameplate
data.
Code
Name
Causes
Possible Solutions
Er-05
No-Load Current Error
The Auto-Tuning results were not in the applicable
parameter setting range.
Auto-Tuning did not complete in a pre-set length of
time.
•
Examine and repair motor wiring.
•
Disconnect the machine from the motor and do Rotational Auto-
Tuning again.
The motor nameplate data entered during Auto-
Tuning is incorrect.
•
Make sure that the input motor nameplate data is correct.
•
Do Auto-Tuning again and correctly set the motor nameplate
data.
Rotational Auto-Tuning was done with a load that
was more than 30% of the rating connected to the
motor.
•
Disconnect the machine from the motor and do Rotational Auto-
Tuning again.
•
If you cannot uncouple the motor and load, make sure that the
load is less than 30% of the motor rating. If a mechanical brake
is installed in the motor, release the brake during Rotational
Auto-Tuning.
Code
Name
Causes
Possible Solutions
Er-08
Rated Slip Error
The motor nameplate data entered during Auto-
Tuning is incorrect.
•
Make sure that the input motor nameplate data is correct.
•
Do Auto-Tuning again and correctly set the motor nameplate
data.
Auto-Tuning did not complete in a pre-set length of
time.
The Auto-Tuning results were not in the applicable
parameter setting range.
•
Examine and repair the motor wiring.
•
If the motor and machine are connected during Rotational Auto-
Tuning, decouple the motor from the machinery.
Rotational Auto-Tuning was done with a load that
was more than 30% of the rating connected to the
motor.
•
Disconnect the machine from the motor and do Rotational Auto-
Tuning again.
•
If you cannot uncouple the motor and load, make sure that the
load is less than 30% of the motor rating. If a mechanical brake
is installed in the motor, release the brake during Rotational
Auto-Tuning.
Содержание HV600
Страница 14: ...i 2 Using the Product Safely 14 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 20: ...1 2 Catalog Code and Nameplate Check 20 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 34: ...2 7 Removing Reattaching Covers 34 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 40: ...Page Intentionally Blank...
Страница 154: ...5 11 Diagnosing and Resetting Faults 154 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 170: ...6 7 Periodic Inspection and Maintenance 170 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 266: ...7 16 U Monitors 266 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 290: ...8 4 Other Embedded Communication Protocols 290 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...