76
YASKAWA
TOEPC71061732E HV600 Drive Installation & Primary Operation
■
208 V Class Branch Circuit Protection
Table 12.2 Factory-Recommended Branch Circuit Protection: 208 V Class
Drive Model
Semiconductor Protection Fuse
Model
Manufacturer: EATON/Bussmann
Maximum Applicable Motor Output
kW (HP)
Class J or T Time Delay Fuse
Rated Current
A
2011
FWH-40B
2.2 (3)
17.5
2017
FWH-45B
3.7 (5)
25
2024
FWH-80B
5.5 (7.5)
40
2031
FWH-125B
7.5 (10)
50
2046
FWH-125B
11 (15)
80
2059
FWH-175B
15 (20)
100
2075
FWH-200B
18.5 (25)
125
2088
FWH-225A
22 (30)
150
2114
FWH-225A
30 (40)
175
2143
FWH-250A
37 (50)
250
2169
FWH-275A
45 (60)
300
2211
FWH-600A
55 (75)
350
2273
FWH-800A
75 (100)
450
■
480 V Class Branch Circuit Protection
Table 12.3 Factory-Recommended Branch Circuit Protection: 480 V Class
Drive Model
Semiconductor Protection Fuse
Model
Manufacturer: EATON/Bussmann
Maximum Applicable Motor Output
kW (HP)
Class J or T Time Delay Fuse
Rated Current
A
4005
FWH-25A14F
2.2 (3)
8
4008
FWH-30A14F
3.7 (5)
12
4011
FWH-40B
5.6 (7.5)
17.5
4014
FWH-45B
7.5 (10)
20
4021
FWH-60B
11.2 (15)
35
4027
FWH-80B
14.9 (20)
45
4034
FWH-100B
18.6 (25)
50
4040
FWH-125B
22 (30)
70
4052
FWH-150B
30 (40)
90
4065
FWH-200B
37 (50)
110
4077
FWH-225A
45 (60)
125
4096
FWH-225A
56 (75)
150
4124
FWH-225A
75 (100)
200
4156
FWH-325A
93 (125)
250
4180
FWH-500A
112 (150)
300
4240
FWH-600A
149 (200)
400
4302
FWH-700A
186 (250)
500
◆
Low Voltage Wiring for Control Circuit Terminals
You must provide low voltage wiring as specified by the National Electric Code (NEC), the Canadian Electric Code,
Part I (CEC), and local codes. Yaskawa recommends the NEC class 1 circuit conductor. Use the UL Listed class 2
power supply for external power supply.