5.10 o: Keypad-Related Settings
364
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
o2-04 Setting
Drive Model
A6
4156
A7
4180
o2-04 Setting
Drive Model
A8
4240
A9
4302
■
o2-05: Home Mode Freq Ref Entry Mode
No.
(Hex.)
Name
Description
Default
(Setting Range)
o2-05
(0509)
Home Mode Freq Ref Entry
Mode
Sets the function that makes it necessary to push
to use the keypad to change the frequency
reference value while in Drive Mode.
0
(0, 1)
0 : ENTER Key Required
You must push
to use the keypad to change the frequency reference value.
1 : Immediate / MOP-style
The frequency reference changes when you enter it with the keypad. This then changes the output frequency. It is not
necessary to push
. The drive keeps the frequency reference for 5 seconds after you use
and
on the
keypad to change the frequency reference value.
■
o2-06: Keypad Disconnect Detection
No.
(Hex.)
Name
Description
Default
(Range)
o2-06
(050A)
Keypad Disconnect
Detection
Sets the function that stops the drive if you disconnect the keypad connection cable from the drive or
if you damage the cable while the keypad is the Run command source.
1
(0, 1)
If the keypad installed to the drive is disconnected, this parameter will continue to operate.
This parameter is enabled in these conditions:
•
b1-02 = 0 [Run Command Selection 1 = Keypad]
•
In HAND Mode
0 : Disabled
The drive continues operation if it detects a keypad disconnection.
1 : Enabled
When the drive detects a keypad disconnection, the drive detects
oPr [Keypad Connection Fault]
, and stops
operation. The motor coasts to stop.
■
o2-09: Region Code
No.
(Hex.)
Name
Description
Default
(Range)
o2-09
(050D)
Reserved
-
-
■
o2-19: Parameter Write during Uv
No.
(Hex.)
Name
Description
Default
(Range)
o2-19
(061F)
Parameter Write during Uv
Enables and disables the function to change parameter settings during a
Uv [DC Bus Undervoltage]
condition.
0
(0, 1)
0 : Disabled
1 : Enabled
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...