USER MANUAL 

 
 
 
 
 
 

SOLAR PUMPING MPPT DYNAMIC 

SD500 Series 

 

 

Document APR0006 

 

 
 
 
 

 
 
 
 
 
 
 

 
 
 
 
 
 
 
 

Содержание SD 500 Series

Страница 1: ...Page 1 of 7 User Manual Solar Pumping SD500 Document APR0006 USER MANUAL SOLAR PUMPING MPPT DYNAMIC SD500 Series Document APR0006...

Страница 2: ...Page 2 of 7 User Manual Solar Pumping SD500 Document APR0006 INDEX INTRODUCTION 1 OPERATION 2 DESCRIPTION OF GROUP G26 3 OTHER PARAMETERS TO MODIFY 4 CONECTIONS...

Страница 3: ...imum MPPT used in Power Electronics Solar Inverters and which has been Implemented into the application of solar pumping The basic operation is based on the dynamic variation of the speed reference wh...

Страница 4: ...er go below this value Although the default value is set to 540v adjust to suit the solar field and the motor in question Screen 2 T IntMPPT Description INTERVAL EXECUTION MPPT Units s Range 0 to 20 F...

Страница 5: ...scription START FACTOR MPPT Units Range 75 to 100 FUNCTION Indicates the value on which the MPPT algorithm will start which respect to the drive BUS voltage It is set at 85 as default value Screen 6 T...

Страница 6: ...PROG PUMP G4 INPUTS G4 1 1 CONTROLMODE1 5 PLC G23 PLC G23 1 Wr DAT1 0x6 G23 2 Wr DAT2 0x388 G23 3 Wr DAT3 0x389 G23 4 Wr DAT4 0x1113 G23 9 Rd DT1 0x315 G23 10 Rd DT2 0x316 G23 11 Rd DT3 0x123B G23 12...

Страница 7: ...r Pumping SD500 Document APR0006 4 CONNECTION SCHEME Only the start stop signal must be connected to the PLC DI1 it s not necessary to connect any signals at the inputs outputs of the inverter Termina...