1-17
Continued
1.4 ELECTRICAL INSTALLATION
L1 ( R )
L2 ( S )
L3 ( T )
FREQUENCY
PULSE TRAIN INPUT
(MAX 30KHz)
SETTING POWER SUPPLY
(+12V, 20mA) (See Note 2)
REFERENCE
FREQUENCY
SETTING
POT
(0 to 10V, 20K‰ /
4 to 20mA, 250‰)
MIN
SW1
SW2
PNP
NPN
OFF
V
1 ON
I
2
MAX
P1
PC
B2
B1
—
+2
+1
AC
MOTOR
T1 ( U )
T2 ( V )
T3 ( W )
MCCB
L1
L2
L3
S1
RUN
LOGIC
COMMON
TERMINAL
FREQUENCY
REF.
MULTI-FUNCTION
PHOTOCOUPLER
OUTPUT
48V, 50mA OR LESS
3-PHASE
POWER SUPPLY
(Use L1 (R) and
L2 (S) for
single-phase
input)
MULTI-FUNCTION
OUTPUT CONTACT
250VAC, 1A OR LESS
30VDC, 1A OR LESS
SHIELD
CONNECTION
ANALOG MONITOR
STOP
S2
S4
S3
S5
S6
FAULT
RESET
MULTI-STEP
SPEED REF 1
S7
SC
FC
OV
FS
RP
FR
R+
R-
S+
S-
AM
AC
FM
ANALOG OUTPUT
MONITOR 0 to +10VDC
OUTPUT
FREQUENCY
MULTI-FUNCTION
CONTACT INPUT
MA
MB
MC
RUNNING
FAULT
FOR DYNAMIC BRAKING
(See Note 6)
FOR DC REACTOR
(See Note 7)
(See Note 5)
*
P2
SPEED
COINCIDENCE
*
*
(See Note 8)
(See Note 5)
MODBUS
COMMUNICATIONS
RS485/422
19.2 KBPS MAX.
(See Note 4)
(See Note 1)
1RH
MANUAL
SPEED
2K‰
0-10VDC
or
4-20mA
1OL (See Note 3)
*
*
*
*
–
+
1OL
See
Note 3)
1R
2K‰
MULTI-STEP
SPEED REF 2
JOG REFERENCE
MODBUS
(TERMINAL
RESISTANCE:
120‰, 0.5W)
FIG. 1-10
FORWARD/
REVERSE
(Note that drive must
be derated by 50%)
GPD 315/V7
GPD 315/V7-4x
OR
Figure 1-6. Standard Connections (3-Wire Control)
(Parameter n001 set to “11”)
H. Inspection. After wiring is complete, verify that:
All wiring is correctly installed.
Excess screws and wire clippings are removed from inside of unit.
Screws are securely tightened.
Exposed wire does not contact other wiring or terminals.
If a FWD or REV run command is given from the control
circuit terminal when the operation method selection
function ( n003 ) is set to “ 1 ” and the “LO/RE” selection
is set to “RE”, the motor will start automatically as soon
as power is applied to the main circuit.
CAUTION
Содержание GPD315/V7-4X
Страница 1: ...GPD 315 V7 and V7 4X Technical Manual...
Страница 4: ......
Страница 20: ...xvi...
Страница 22: ......
Страница 35: ...1 13 Continued 1 4 ELECTRICAL INSTALLATION U V W Figure 1 4 Installation of Line Filter and Drive...
Страница 40: ...1 18...
Страница 52: ...3 2...
Страница 56: ...4 4...
Страница 101: ...5 45 PID Block Diagram...
Страница 130: ...A1 8...
Страница 134: ...A3 2...
Страница 136: ...A4 2...
Страница 146: ...A6 6...
Страница 150: ...A7 4...
Страница 154: ...A8 4...
Страница 158: ......
Страница 160: ......