2-6
IMPORTANT
2-wire or 3-wire sequence selection must be made prior to any other adjustments (Parameter n001).
2.3 V/f STARTUP PROCEDURE
DIGITAL OPERATOR
DESCRIPTION
KEY SEQUENCE
DISPLAY
Table 2-2. V/f Startup Procedure
Set the highest parameter
access level.
This will allow all parameters
to be viewed and set.
Press
key until the
LED is lit
on the digital operator.
PRGM
DSPL
Set drive for V/f control.
This is accomplished by
setting n002 = 0
Press then .
DATA
ENTER
V
PRGM
PRGM
PRGM
PRGM
PRGM
PRGM
PRGM
Then press
.
DATA
ENTER
Use the
&
keys to set a “0”
in the display.
V
V
Press .
DATA
ENTER
Press .
DATA
ENTER
Press three
times.
V