9-4 Command Priority
Table 9-2: Set up for External Terminals Control
This table indicates the functions or commands that can be accessed via serial communication,
external terminals, or the Digital Operator when the drive is set up for external terminal control
(b1-02 = 1). The ìOî indicates that the function is Operable from that source, and ìn/aî indicates
that the function is not available from that source.
From
Regis
ter
Bit
No.
Data Description
Function
Availability
001h
0
Run Forward
n/a
1
Run Reverse
n/a
2
Multi-function Input (terminal 3)
O
3
Multi-function Input (terminal 4)
O (1)
4
Multi-function Input (terminal 5)
O
5
Multi-function Input (terminal 6)
O
SERIAL
6
Multi-function Input (terminal 7)
O
COMM.
7
Multi-function Input (terminal 8)
O
8-15
unused
—
007h
0-15
Analog Output 1 Setting
n/a
008h
0-15
Analog Output 2 Setting
n/a
009h
0
Multi-function Output (terminals 9 & 10)
n/a
1
Multi-function Output (terminals 25 & 27)
n/a
2
Multi-function Output (terminals 26 & 27)
n/a
3-5
—
6
Fault Contact (terminals 18 & 20)
n/a
7
Fault Contact Closed (effective when bit 6=1)
n/a
Forward Run (2 wire); Run Command (3 wire)
O
Reverse Run (2 wire); Stop Command (3 wire)
O
multi-function input terminal 3
(2)
EXTERNAL
multi-function input terminal 4
(2)
TERMINALS
multi-function input terminal 5
(2)
multi-function input terminal 6
(2)
multi-function input terminal 7
(2)
multi-function input terminal 8
(2)
Run Command
n/a
Stop Command
O (3)
DIGITAL
Reverse Run Command
n/a
OPERATOR
Local / Remote
O (4)
Jog Command
n/a
Fault Reset
O (1)
Notes:
1. Fault Reset (Multi-function Input terminal 4 default setting) is only effective only when external
terminal satisfies the following conditions:
2 wire mode - Both forward run (term. 1) and reverse run (term. 2) commands are
closed, or open in stopped condition.
3 wire mode - Run command (term. 1) or stop command (term. 2) is open in stopped
condition.
2. The availability of the multi-function input terminals vary depending upon the setting of A1-02
(Control Method). See technical manual TM 4515.
3. Effective only when o2-02 is ì1î.
4. Effective when o2-01 is î1î.