A6-6
5 . The Braking Transistor Unit and Remote Mount Resistor Unit MUST BE GROUNDED.
Observe the following precautions:
•
Ground units per local electrical codes.
•
If the installation requires the Remote Mount Resistor Unit to be used without its
enclosure (with grounding terminal), ground it by attaching a ground lead
at one of the mounting screws.
•
Grounding resistance of the Braking Transistor Unit should be 100 ohms or less.
(1)
Fuse required only if UL/CUL certification is needed. See separate instruction sheet
02Y00025-0393 for details.
Figure A6-4. Wiring Single Braking Transistor Unit and Remote Mount Resistor Unit to Drive
(GPD506V-A054 and -A068 [CIMR-P5M20111F and 20151F], -B380 [CIMR-P5M41850F],
and CIMR-P5M50301F thru 50371F).
T1
T2
T3
L1 (R)
L2 (S)
L3 (T)
T1 (U)
T2 (V)
T3 (W)
CONTROL
PCB
PART OF USER SUPPLIED
EXTERNAL CIRCUIT
B
P
N
3
1OL
1M
1M
1M
CB
L1
L2
L3
120VAC
FAULT
CONTACT
THRX
RC
IFU
(1)
See Note
(1)
1M
RC
1M
THRX
POWER
ON
POWER
OFF
1
1THG
B
P
P
o
GND
(E)
4
–
+ 3
GPD 506/P5
BRAKING
TRANSISTOR
UNIT
REMOTE
MOUNT
RESISTOR
UNIT
S3
SC
Содержание GPD-506V