SIEPC71061737B GA800 Drive Technical Reference
Table 12.44 DI-A3 Terminal Function Selection
Terminal
Block
Terminal
Name
BCD, Signed
[F3-01 = 0 to 5]
BCD, Unsigned
[F3-01 = 6]
Binary, Signed
[F3-01 = 7]
8-bit
[F3-03 = 0]
12-bit
[F3-03 = 1]
16-bit
[F3-03 = 2]
8-bit
[F3-03 = 0]
12-bit
[F3-03 = 1]
16-bit
[F3-03 = 2]
TB2
D0
1 digit (0 -
9)
1
1 digit (0 -
9)
1
1 digit (0 -
9)
1
1 digit (0, 2,
4, 6, 8)
2
bit 0
bit 0
bit 0
D1
2
2
2
4
bit 1
bit 1
bit 1
D2
4
4
4
8
bit 2
bit 2
bit 2
D3
8
8
8
2 digits (0 -
9)
1
bit 3
bit 3
bit 3
D4
2 digits (0 -
15)
1
2 digits (0 -
9)
1
2 digits (0 -
9)
1
2
bit 4
bit 4
bit 4
D5
2
2
2
4
bit 5
bit 5
bit 5
D6
4
4
4
8
bit 6
bit 6
bit 6
D7
8
8
8
3 digits (0 -
9)
1
bit 7
bit 7
bit 7
TB3
D8
-
-
3 digits (0 -
15)
1
3 digits (0 -
9)
-
2
-
bit 8
bit 8
D9
-
2
-
4
-
bit 9
bit 9
DA
-
4
-
8
-
bit 10
bit 10
DB
-
8
-
4 digits (0 -
9)
1
-
bit 11
bit 11
DC
-
-
-
-
4 digits (0 -
15)
-
2
-
-
bit 12
DD
-
-
-
4
-
-
bit 13
DE
-
-
-
8
-
-
bit 14
DF
-
-
-
5 digits (0 -
3)
1
-
-
bit 15
TB1
SI
SIGN (encoded) signal
0: Forward run, 1: Reverse run
2
SIGN (encoded) signal
0: Forward run, 1: Reverse run
SE
SET (loaded) signal
1: Loads the value set for D0 to DF and SI.
SP
Internal power supply: 24 V ± 5%
SC
Input signal common
SN
Internal power supply common: 0 V
SD
Cable sheath connection terminal (ungrounded)
FE
Cable sheath connection terminal (grounded)
*1
Setting
F3-03 = 2 [Digital Input Data Length Select = 16-bit]
enables
F3-01 = 6 [Digital Input Function Selection = BCD (5-digit), 0.01
Hz]
and a frequency between 0.00 Hz to 399.8 Hz can be set by the BCD. Note that terminal SI is also used as for data bits. Negative
commands cannot be input as encoding information (positive/negative) cannot be added to the data.
The minimum bit value for the first BCD digit is 2. For this reason, 0.02 Hz is the smallest setting unit available for this frequency setting.
An
oPE05 [Run Cmd/Freq Ref Source Sel Err]
occurs when
F3-03 ≠ 2
while
F3-01 = 6
.
*2
The most significant digit can be set to a value between 0 to 15 when using
“
BCD, Signed
”
. Other digits can be set to a value between 0 to
9.
■
F3-10: Terminal D0 Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
F3-10
(0BE3)
Expert
Terminal D0 Function
Selection
Sets the function for terminal D0 of the DI-A3 option when
F3-01 = 8 [Digital Input Function
Selection = Multi-Function Digital Input]
.
F
(1 - 19F)
■
F3-11: Terminal D1 Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
F3-11
(0BE4)
Expert
Terminal D1 Function
Selection
Sets the function for terminal D1 of the DI-A3 option when
F3-01 = 8 [Digital Input Function
Selection = Multi-Function Digital Input]
.
F
(1 - 19F)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...