Required Short Circuit Protection
Table 12.2 Required Short Circuit Protection for FP605 AC Drives (240 V Class)
Drive
Catalog
Code
FP65U
Drive Mounted without
Supplemental Enclosure
(Using Type 1 Kit)
Drive Mounted in Supplemental Enclosure
Any Size Protected Enclosure
(Ventilated or Non-Ventilated)
Restricted Size Protected Enclosure
(Ventilated Only)
Semiconductor
Fuse
Part Number
(Permitted Only
in Type 1 Kit)
Manufacturer:
Eaton/Bussmann
Class CC, J, or T
Fuse
Maximum Amps
Semiconductor
Fuse
Part Number
Manufacturer:
Eaton/Bussmann
Class CC, J, or T
Maximum Amps
Class CC, J, or T
Fuse
Maximum Amps
Maximum
Amps
Part Number
Manufacturer:
Schneider
Enclosure Volume
Minimum (in
3
)
External
Heatsink
Internal
Heatsink
2011
Not allowed.
Does not support
internal fuses for
these drive models.
17.5
FWH‐40B
17.5
Enclosure volume
not restricted.
Refer to the values
in the column to the
left for fuses.
25
HLL36030M71
3056
3056
2017
25
FWH‐45B
25
40
HLL36030M71
3056
3056
2024
40
FWH‐80B
40
60
HLL36050M72
3056
3056
2031
50
FWH‐125B
50
75
HLL36050M72
3056
3056
2046
80
FWH‐125B
80
110
HLL36100M73
5520
5520
2059
100
FWH‐175B
100
125
HLL36100M73
5520
5520
2075
125
FWH‐200B
125
175
HLL36150M74
5520
5520
2088
150
FWH‐225A
150
200
HLL36150M74
5520
5520
2114
200
FWH‐225A
200
250
HLL36150M74
5520
5520
2143
250
FWH‐250A
250
350
JLL36250M75
21582
14657
2169
250
FWH‐275A
250
400
JLL36250M75
21582
14657
2211
350
FWH‐600A
350
500
LAL3640036M
or
LLL36400M37X
52800
14657
2273
450
FWH‐800A
450
600
LAL3640036M
or
LLL36400M37X
52800
14657
2343
600
FWH-1000A
or
FWH-1000B
600
700
PLL34060M68
52800
52800
2396
700
FWH-1000A
or
FWH-1000B
700
800
PLL34060M68
52800
52800
*1
Protection device must be in same enclosure with drive.
*2
Class T fuses are fast-acting (non‐time-delay) only. Class CC and J can be either time-delay or non-time-delay.
*3
Protection device and drive permitted in same or separate enclosure.