Specifications C - 2
Standard Drive and Bypass Specifications
The standard Drive and Bypass specifications are listed in the following tables.
208 VAC
Table C.1 208 VAC Drive and Bypass Specifications
Bypass Model Number E7L_ *
D003
D004
D007
D010
D016
D024
D030
D046
D059
D074
Motor HP
208V
0.5/0.75
1
1.5/2
3
5
7.5
10
15
20
25
Bypass rated output current (A)
3.5
4.6
7.5
10.6
16.7
24.2
30.8
46.2
59.4
74.8
Drive Model Number CIMR-E7U
22P2
22P2
22P2
22P2
23P7
25P5
27P5
2011
2015
2018
Drive rated output capacity (kVA)
1.4
1.8
3.0
4.1
6.4
8.8
12.0
18.0
23.0
29.0
Drive rated output current (A)
3.6
4.6
7.8
10.8
16.8
23.0
31.0
46.2
59.4
74.8
Drive max. output voltage (V)
3-phase; 200, 208, 220, or VAC (Proportional to input voltage)
Drive max. output frequency (Hz)
120 Hz
Rated voltage (V)
Rated frequency (Hz)
3-phase, 200/208/220 VAC, 50/60 Hz
Rated input current (A)
4.3
5.5
9.4
13
20
24
37
53
70
89
Allowable voltage fluctuation
+ 10%, - 15%
Allowable frequency fluctuation
±5%
Measures for
power supply
harmonics
DC Reactor
Optional
12-Pulse
Rectification
Not possible
Note: The maximum applicable motor output is given for a standard 4-pole motor. When selecting the actual motor and Drive, be sure that the
Bypass and Drive's rated output current is equal to, or greater than, the motor's rated current.
A phase-shifting transformer is required on the power supply for 12-pulse rectification.
* Only 208V model numbers are shown.
Co
nt
ro
l
ch
ar
ac
te
ris
tic
s
P
ower
s
upply
ch
ar
act
er
is
tic
s
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com