Capacity Related Parameters B - 2
Drive Capacity
Parameter o2-04 sets the Drive capacity according to the model number. Parameter o2-04 will need to be adjusted when
replacing a control board.
If a Control PCB is changed, the first time the Drive is powered up, parameter o2-04 must be set to the appropriate value listed
in
Table B.1
for the Drive model number. After properly setting parameter 02-04, a 2-wire or 3-wire initialization must be
performed by setting parameter A1-03=2220 or A1-03=3330, respectively.This will automatically program the values of all
other parameters listed in
Table B.2
to the factory settings for that particular Drive rating.
Table B.1 Drive Capacity Selection
Voltage
Model Number
o2-04 Setting
Nominal Hp
208 VAC
CIMR-E7U20P4
0
0.5/0.75
CIMR-E7U20P7
1
1
CIMR-E7U21P5
2
1.5/2
CIMR-E7U22P2
3
3
CIMR-E7U23P7
4
5
CIMR-E7U25P5
5
7.5
CIMR-E7U27P5
6
10
CIMR-E7U20111
7
15
CIMR-E7U20151
8
20
CIMR-E7U20181
9
25
480 VAC
CIMR-E7U40P4
20
0.5/0.75
CIMR-E7U40P7
21
1
CIMR-E7U41P5
22
1.5/2
CIMR-E7U42P2
23
3
CIMR-E7U43P7
24
5
CIMR-E7U45P5
26
7.5
CIMR-E7U47P5
27
10
CIMR-E7U4009
28
15
CIMR-E7U4011
28
20
CIMR-E7U4015
29
25
CIMR-E7U4018
2A
30
CIMR-E7U4024
2C
40
CIMR-E7U4030
2C
50
.