YASKAWA
TOEPC71061723A YASKAWA AC Drive CR700 Quick Start Guide
17
Note:
Contact Yaskawa or your nearest sales representative for details about the drive models that can be installed on its side and their
operating conditions.
A - Upright installation
B - Horizontal installation
Figure 8.1 Installation Orientation
■
Single Unit Installation
Install the drive with the clearances specified in
to guarantee sufficient space for wiring and airflow.
A - At least 50 mm (2 in.)
B - At least 30 mm (1.2 in.) on both sides
C - At least 120 mm (4.7 in.) above and below
D - Airflow direction
Figure 8.2 Drive Installation Space (Single Unit)
■
Mounting Multiple Drives Side-by-Side
Drive models 2003xB to 2075xB and 4002xB to 4039xB can take advantage of side-by-side installation.
When installing other drive models, ensure that enough space for single unit installation is placed around each
drive.
When performing side-by-side installation of drives, ensure that enough space is provided for the installation of
the drives with the clearances specified in
. Set
L8-35 [Installation Method Selection]
to
1 [Side-by-Side
Mounting]
.
Derate the output current to match the ambient temperature.
EN