104
YASKAWA
TOEPC71061723A YASKAWA AC Drive CR700 Quick Start Guide
Screw Size
Screw Shape
Adapter
Bit
Torque Driver Model
(Tightening Torque)
Torque Wrench
Model
Manufacturer
M6
Hex socket cap
(WAF: 5 mm)
Bit
SF-BIT-HEX 5-50
PHOENIX CONTACT
-
5 - 9 N∙m
(44.3 - 79.9 lbf∙in)
Minus (-)
Bit
SF-BIT-SL 1,2X6,5-70
PHOENIX CONTACT
-
3 - 3.5 N∙m
(26.6 - 31.0 lbf∙in)
M8
Hex socket cap
(WAF: 6 mm)
Bit
SF-BIT-HEX 6-50
PHOENIX CONTACT
-
8 - 12 N∙m
(70.8 - 106.2 lbf∙in)
M10
Hex socket cap
(WAF: 8 mm)
Bit
SF-BIT-HEX 8-50
PHOENIX CONTACT
-
12 - 14 N∙m
(106.2 - 123.9 lbf∙in)
*1
When wiring drive models 2047, 4075, and smaller, select the correct tools for the wire gauge.
*2
Use 6.35 mm (0.25 in) bit socket holder.
*3
Use a torque wrench that can apply this torque measurement range.
■
Wire Gauges and Tightening Torques
Refer to
Three-Phase 200 V Class on page 104
and
Three-Phase 400 V Class on page 108
for the recommended
wire gauges and tightening torques of the main circuit terminals.
Comply with local standards concerning appropriate wire gauges in the region where the drive is used.
Note:
•
The recommended wire gauges based on drive continuous current ratings using 75 °C (167 °F) 600 V class 2 heat resistant indoor PVC
wire. Assume the following usage conditions:
–
Ambient temperature: 40 °C (104 °F) or lower
–
Wiring distance: 100 m (3281 ft.) or shorter
–
Rated current value
•
Use ter1, +2, +3, -, B1, and B2 to connect peripheral options such as a DC reactor or a braking resistor. Do not connect
anything other than optional devices.
•
Refer to the specific instruction manual of each device for wire gauges when connecting peripheral devices or options to ter1,
+2, +3, -, B1, and B2. Contact Yaskawa or your nearest sales representative if the recommended wire gauges for the peripheral devices
or options are out of the range of the applicable gauge for the drive.
•
Use UL approved closed-loop crimp terminals on the drive main circuit terminals in drive models 2215 to 2415 and 4180 to 4605. Use
the tools recommend by the terminal manufacturer to ensure that the terminals are correctly fastened.
Three-Phase 200 V Class
Table 16.2 Main Circuit Wire Gauges and Tightening Torques (200 V Class)
Model
Terminal
Recomm. Gauge
AWG, kcmil
Applicable Gauge
(IP20 Applicable
Gauge
)
AWG, kcmil
Wire Stripping
Length
mm
Terminal Screw
Tightening
Torque
N
∙
m (lbf
∙
in)
Terminal
Screw Size
Shape
2003
R/L1, S/L2, T/L3
14
14 - 6
(14 - 6)
10
M4
Slotted (-)
1.5 - 1.7
(13.5 - 15)
U/T1, V/T2, W/T3
14
14 - 6
(14 - 6)
10
M4
Slotted (-)
1.5 - 1.7
(13.5 - 15)
-, +1, +2
14
14 - 3
(14 - 3)
18
M5
Slotted (-)
2.3 - 2.5
(19.8 - 22)
B1, B2
14
14 - 10
(14 - 10)
10
M4
Slotted (-)
1.5 - 1.7
(13.5 - 15)
10
14 - 8
(-)
-
M4
Phillips/slotted
combo
1.2 - 1.5
(10.6 - 13.3)
2005
R/L1, S/L2, T/L3
14
14 - 6
(14 - 6)
10
M4
Slotted (-)
1.5 - 1.7
(13.5 - 15)
U/T1, V/T2, W/T3
14
14 - 6
(14 - 6)
10
M4
Slotted (-)
1.5 - 1.7
(13.5 - 15)
-, +1, +2
14
14 - 3
(14 - 3)
18
M5
Slotted (-)
2.3 - 2.5
(19.8 - 22)
B1, B2
14
14 - 10
(14 - 10)
10
M4
Slotted (-)
1.5 - 1.7
(13.5 - 15)
10
14 - 8
(-)
-
M4
Phillips/slotted
combo
1.2 - 1.5
(10.6 - 13.3)