Order no.
314-6CF23
Operational limit of resistance thermometer ranges
+/-0.6%
Operational limit of resistance thermometer ranges with
SFU
-
Basic error limit thermoresistor ranges
+/-0.4%
Basic error limit thermoresistor ranges with SFU
-
Destruction limit resistance thermometer inputs
max. 15V
Thermocouple inputs
-
Thermocouple ranges
-
Operational limit of thermocouple ranges
-
Operational limit of thermocouple ranges with SFU
-
Basic error limit thermoelement ranges
-
Basic error limit thermoelement ranges with SFU
-
Destruction limit thermocouple inputs
-
Programmable temperature compensation
-
External temperature compensation
-
Internal temperature compensation
-
Technical unit of temperature measurement
°C
Resolution in bit
12
Measurement principle
Sigma-Delta
Basic conversion time
6 ms
Noise suppression for frequency
80 dB
Initial data size
10 Byte
Technical data analog outputs
Number of outputs
2
Cable length, shielded
200 m
Rated load voltage
DC 24 V
Reverse polarity protection of rated load voltage
ü
Current consumption from load voltage L+ (without load)
-
Voltage output short-circuit protection
-
Voltage outputs
ü
Min. load resistance (voltage range)
1 kΩ
Max. capacitive load (current range)
1 µF
Max. inductive load (current range)
30 mA
Output voltage ranges
-10 V ... +10 V
0 V ... +10 V
Operational limit of voltage ranges
+/-0.4%
Basic error limit voltage ranges with SFU
+/-0.3%
VIPA System 300S
+
Hardware description
Technical data
HB140 | CPU | 314-6CF23 | en | 19-01
41