Here end character(s) may be defined or the length set in the FB may be specified as
soon as "End character" is activated at the end ID.
Parameter
Description
Default value
End character 1/2
For communication with end character(s) maximally 2 end
characters may be defined.
The length of the respective telegram is limited by an end
character.
n
Range of values: 0...7Fh/FFh (7/8 data bits)
End character 1:3
(03h=ETX)
End character 2:0
Here the transfer speed may be selected from a selection list.
Parameter
Description
Default value
Baud rate in bit/s
Transfer speed in bit/s
n
Range of values: 300, 600, 1200, 2400, 4800, 9600,
19200, 38400, 57600, 76800
9600
The data between the communication partners are transferred via the serial interface by
means of a character frame. This means that each character may be recognized at the
receiver and the transmission may be checked for errors.
Please regard that all the following parameters must have the same set-
tings on every communication partner.
Parameter
Description
Default value
Data bits
Number of bits onto which a character is mapped.
n
Range of values: 7, 8
8
Stop bits
When data is transmitted, stop bits are appended to each
character to be sent in order to signal the end of a char-
acter.
n
Range of values: 1, 2
1
Parity
The addition of its value "0" or "1" brings the value of all
the bits (data bits and parity bit) up to a defined status.
n
Range of values: none, odd, even
even
Data flow control synchronizes data transmission when one communication partner works
faster than the other with ASCII. Here the type of data flow control may be set and its
associated parameters.
At half-duplex parameterization with RS485 data flow control is not pos-
sible.
Send with end character
Speed
Character frames
ASCII transmission
VIPA System 300S
Communication protocols
ASCII > ASCII - Parameter
HB130 | CP | 341-1CH01 | en | 18-40
39