At the CP interface the wiring of the receiver is realized as follows:
Parameter
Description
None
(Default value: not activated)
No preassignment of the receiving lines. This setting
only makes sense with bus-capable special drivers.
Parameter
Description
Signal R(B) 0Volt
Signal R(A) 5Volt
(Break evaluation)
With this preassignment wire break evaluation is pos-
sible at full-duplex operation with RS422.
Parameter
Description
Signal R(B) 5Volt
Signal R(A) 0Volt
(Default value: not activated)
No wire break detection is possible here.
Wiring receiver
VIPA System 300S
Communication protocols
3964(R) > 3964(R) - Parameter
HB130 | CP | 341-1CH01 | en | 18-40
47