A.18 Defaults by Drive Model
The following tables show parameters and default settings that change with the drive model selection (o2-04).
Table A.7 600 V Class Drives Default Settings by Drive Model
No.
Name
Unit
–
Model
–
5A0003
5A0004
5A0006
5A0009
5A0011
o2-04
Drive Model Selection
Hex.
C3
C4
C5
C7
E2-11
Motor Rated Power
kW
(HP)
1.5
(2)
2.2
(3)
3.7
(5)
5.5
(7.5)
7.5
(10)
b3-04
V/f Gain during Speed Search
%
100
100
100
100
100
b3-06
Output Current 1 during Speed Search
–
0.5
0.5
0.5
0.5
0.5
b8-04
Energy Saving Coefficient Value
–
494.4
415.3
320.2
239.95
199.86
C6-02
Carrier Frequency Selection
–
7
7
7
7
7
E2-01
Motor Rated Current
A
2.7
3.9
6.1
9
11
E2-02
Motor Rated Slip
Hz
2.5
3.0
2.7
1.5
1.3
E2-03
Motor No-Load Current
A
0.8
1.2
1.8
2.7
3.3
E2-05
Motor Line-to-Line Resistance
Ω
13.72
8.825
4.936
2.601
1.446
E2-10
Motor Iron Loss for Torque Compensation
W
53
77
130
193
263
L2-02
Momentary Power Loss Ride-Thru Time
s
0.2
0.3
0.5
0.5
0.8
L2-03
Momentary Power Loss Minimum Baseblock
Time
s
0.5
0.5
0.8
0.8
1
L2-04
Momentary Power Loss Voltage Recovery
Time
s
0.5
0.5
0.6
0.7
0.8
L3-24
Motor Acceleration Time for Inertia
Calculations
s
0.166
0.145
0.154
0.168
0.175
L8-02
Overheat Alarm Level
°C
110
110
110
110
115
L8-35
Installation Method Selection
–
2
2
2
2
2
L8-38
Carrier Frequency Reduction Selection
–
2
2
2
2
2
n1-03
Hunting Prevention Time Constant
ms
10
10
10
10
10
No.
Name
Unit
Default Settings
–
Model
–
5A0017
5A0022
5A0027
5A0032
o2-04
Drive Model Selection
Hex.
CA
CC
CD
CE
E2-11
Motor Rated Power
kW (HP)
11
(15)
15
(20)
18.5
(25)
22
(30)
b3-04
V/f Gain during Speed Search
%
100
100
100
100
b3-06
Output Current 1 during Speed Search
–
0.5
0.5
0.5
0.5
b8-04
Energy Saving Coefficient Value
–
172
154
140
129
C6-02
Carrier Frequency Selection
–
7
7
7
7
E2-01
Motor Rated Current
A
17
22
27
32
E2-02
Motor Rated Slip
Hz
1.7
1.6
1.67
1.7
E2-03
Motor No-Load Current
A
5.1
6.6
8.1
9.6
E2-05
Motor Line-to-Line Resistance
Ω
1.17
0.9
0.66
0.52
E2-10
Motor Iron Loss for Torque Compensation
W
385
440
508
586
L2-02
Momentary Power Loss Ride-Thru Time
s
1
2
2
2
L2-03
Momentary Power Loss Minimum Baseblock Time
s
1
1.2
1.2
1.2
L2-04
Momentary Power Loss Voltage Recovery Time
s
0.9
1
1
1
L3-24
Motor Acceleration Time for Inertia Calculations
s
0.27
0.24
0.32
0.36
L8-02
Overheat Alarm Level
°C
120
120
115
115
L8-35
Installation Method Selection
–
2
2
2
2
L8-38
Carrier Frequency Reduction Selection
–
2
2
2
2
n1-03
Hunting Prevention Time Constant
ms
10
10
10
10
A.18 Defaults by Drive Model
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual
241
A
Parameter List