Application Overview 2-13
#
Prohibit Frequencies - nciProFreq1, nciProFreq2, nciProFreqBW
These properties define bands of prohibited frequencies, selected to avoid certain areas of resonant motor vibration. Two separate bands can be
defined, with a common bandwidth. When this feature is selected, the motor is accelerated and decelerated through the prohibited areas. These
properties configure the drive as described below:
Table 2.14 - Prohibit Frequencies - nciProFreq1, nciProFreq2, nciProFreqBW
Property Name
Variable Type
Default
Parameter
Description
nciProFreq1
SNVT_freq_hz
0 Hz
d3-01
Sets the center frequency for the first band of prohibit frequencies.
nciProFreq2
SNVT_freq_hz
0 Hz
d3-02
Sets the center frequency for the second band of prohibit frequencies.
nciProFreqBW SNVT_freq_hz 1.0
Hz d3-04 Sets the bandwidth for prohibit frequencies.
#
Automatic Restarts - nciAutoRstrt
This configuration property defines the number of automatic restarts that will be attempted under certain fault conditions.
Table 2.15 - Automatic Restarts - nciAutoRstrt
Property Name
Variable Type
Default
Parameter
Description
nciAutoRstrt SNVT_count 0
L5-01
Selects the number of times the drive attempts to automatically restart
after certain faults.
!
Restartable Faults
%
Overcurrent (oC)
%
Overvoltage (ou)
%
Undervoltage (Uu1)
%
Ground Fault (GF)
!
Non-Restartable Faults
%
Overload (oL_)
%
External (EF_)
%
Hardware (CPF_)
%
Fuse Blown (PUF)
%
Overcurrent (oC)
%
Overvoltage (oV) during deceleration
#
Power Loss Ride-Through – nciPLRideThru
Table 2.16 - Drive Configuration Property - nciPLRideThru
Property Name
Variable Type
Default
Parameter
Description
nciPLRideThru
SNVT_count
0.1sec
L2-02
Sets the ride through time at momentary power loss
Table 2.17 - nciPLRideThru
nciPLRideThru
Value
Remarks
0
Disabled
Momentary power loss ride through is disabled
0.1 ~ 25.5sec
Enabled
The ride through time at momentary power loss *
* Parameter L2-01 must be set to 1 in order for this variable to be available. A setting of 0 or 2 in parameter L2-01 will disable power loss ride
through.
Содержание CIMR-E7 series
Страница 1: ...LONWORKS Option Technical Manual Models CIMR E7 P7 F7 and G7 Document Number TM AFD 20 ...
Страница 5: ...iv This page intentionally left blank ...
Страница 7: ...Installation 1 2 This page intentionally left blank ...
Страница 9: ...Installation 1 4 This page intentionally left blank ...
Страница 19: ...Application Overview 2 2 This page intentionally left blank ...
Страница 38: ...Diagnostics 3 2 This page intentionally left blank ...
Страница 40: ...Diagnostics 3 4 This page intentionally left blank ...