6 Related Parameters
40
YASKAWA ELECTRIC
TOBP C730600 78D YASKAWA AC Drive Option AI-A3 Installation Manual
Figure 29
Figure 30 Using the Option for Multi-Function Analog Inputs
Setting 1: 3 Channels Added Together
To set a combined input, set b1-01 to 3 (Option PCB) or F2-01 to 1 (3 Channels Added
Together).
The resulting value of adding the input from terminals V1 to V3 becomes the frequency
reference.
The following block diagram illustrates combined input. Use parameters F2-02 and F2-03 to
adjust the analog reference gain and bias for combined input.
Figure 30
Figure 31 Combining Inputs for the Frequency Reference
AI-A3
V1 voltage input
(–10 to 10 V)
or
current input
(
4 to 20 mA
)
AI-A3
V2 voltage input
(–10 to 10 V)
or
current input
(
4 to 20 mA
)
AI-A3
V3 voltage input
(–10 to 10 V)
or
current input
(
4 to 20mA
)
Current input
(“I” position)
Voltage input
(“V” position)
Current input
(“I” position)
Voltage input
(“V” position)
Current input
(“I” position)
Voltage input
(“V” position)
H3-13
Primary
filter
Terminal V1 input switch
(S1)
Terminal V2 input switch
(S2)
Terminal V3 input switch
(S3)
H3-13
≠
0
≠
0
≠
0
H3-13
Primary
filter
H3-13
H3-13
H3-13
Primary
filter
0
H3-08
H3-07
10 V
H3-12
H3-11
10 V
Input value (%)
Analog input
Analog input
Analog input
Input value (%)
Input value (%)
H3-04
H3-03
10 V
0
0
0%
100%
100%
-100%
0%
100%
100%
-100%
0%
100%
100%
-100%
Input value is
added to the
function selected
in H3-02
Input value is
added to the
function selected
in H3-10
Input value is
added to the
function selected
in H3-06
AI
+
+
+
+
+
V2
10 V to 10 V
or 4 to 20 mA
V1
10 V to 10 V
or 4 to 20 mA
V3
10 V to 10 V
or 4 to 20 mA
×
1/10
1/10
F2-02
F2-03
Frequency reference
from the option
AI