6 Related Parameters
YASKAWA ELECTRIC
TOBP C730600 41E 1000-Series Option DO-A3 Installation Manual
25
F5-05
(39D)
Terminal P5-PC Output Selection
Sets the function for contact output terminals
M1-M2, M3-M4, and photocoupler output
terminals P1 through P6.
When installed to drive
Default: 6
Range: 0 to 1A7
When installed to D1000
Default: F
Range: 0 to 160
F5-06
(39E)
Terminal P6-PC Output Selection
When installed to drive
Default: 37
Range: 0 to 1A7
When installed to D1000
Default: F
Range: 0 to 160
F5-07
(39F)
Terminal M1-M2 Output
Selection
When installed to drive
Default: F
Range: 0 to 1A7
When installed to D1000
Default: F
Range: 0 to 160
F5-08
(3A0)
Terminal M3-M4 Output
Selection
When installed to drive
Default: F
Range: 0 to 1A7
When installed to D1000
Default: F
Range: 0 to 160
F5-09
(3A1)
DO-A3 Output Mode Selection
0: Output terminals are each assigned
separate output functions.
1: Binary code output
2: Multi-function output (set functions in
parameters F5-01 through F5-08)
When installed to drive
Default: 0
Range: 0 to 2
When installed to D1000
Default: 2
Range: 2
<1> Refer to the unit Instruction Manual for more information on setting the F5 parameters.
No.
(Addr.
Hex)
Name
Description