26
4. How to Use
Air flow adjustment method (for the air curtain type only)
①
Measure the air flow at the blow port of air curtain.
Run exhaust and fan blowers with the operation key and open the door fully. Provide
a guide plate of about 100 mm at the blow port. Divide the opening into five equal
portions and measure the air flow in a center of each of these portions with a wind speed
indicator.
(
Fig.4-3
)
Fig. 4-3
②
From the average of air flow values obtained from five points, calculate the air flow using
[Formula 1] and compare the calculated value with the standard supply air flow (Page
41) for each type. When the air flow thus calculated deviates from the standard value,
adjust it with a damper handle of the ceiling supply duct.
Guide
Wind speed indicator