4 - 44
Setting the Range
Introduction
This is used to set the flow rate measurement range, which means the value
when the electromagnetic output reaches 100%. The lower limit of the range
is zero.
Setting the range
Flow rate:
0.0001 - 99999
Units:
m
3
, l, cm
3
, t, kg, g
Time units: s, min., h, d
When single range is selected
Open the range setup screen by
following the steps to enter the
Engineering Mode.
Touch the key to move the
cursor to the desired digits.
Use the and keys to
change the numbers.
Touch the key to move the
cursor to the time unit. Use the
or key to select the de-
sired unit.
Touch the key to move the
cursor to the flow rate unit.
Use the or key to select
the desired unit.
1
Screen
Procedure
Step
Touch the key to move the
cursor to the "#".
6
5
4
3
2
# 1.4147 m / s
SPAN 10.000 m
3
/ h
# 1.4147 m / s
SPAN 10.000 m
3
/ h
# 2.8294 m / s
SPAN 20.000 m
3
/ h
# 2.8294 m / s
SPAN 20.000 1 / h
# 2.8294 m / s
SPAN 333.33 1 / min
# 2.8294 m / s
SPAN 333.33 1 / min