background image

AB-5963

1

Insertion Dewpoint

Temperature / Humidity Sensor

HTY79X3 / HY79X3

General

Insertion dewpoint temperature / humidity sensor
HTY79X3 series uses a Pt100 platinum film temperature
sensing element and a polymer capacitive film humidity
sensing element (FP3 specially developed by Yamatake)
which ensures highly accurate and reliable tempera-
ture/humidity sensing.    It is designed to be installed in
return air ducts of commercial buildings, in return air
chambers of air handling units or in ventilated shield for
meteorological instruments.    HY79X3 series for sensing
only dewpoint temperature without separate temperature
sensor is also available.

Features

1) Wide sensing range
2) Excellent long term stability
3) Highly resistant to environment
4) Quick response and high repeatability.
5) Easy to install in a duct (bracket prepared)
6) Splash-proof housing (IP54)

     

Models

Model No.

Shape

Type

Power
supply

Humidity

output

Temperature

output

Fixed

Fixed

Description

HTY79

Insertion dewpoint temperature sensor (w/separate
temperature sensor)

HY79

Insertion dewpoint temperature sensor

0

Insertion length: Long

1

Insertion length: Short

3

T

Shared 24 V DC, 24 V AC

1

Humidity output 1-5 V

4

Humidity output 4-20 mA

6

Humidity output 0-10 V

0

W/o temperature sensor

P

Temperature Pt 100

0

0

Specifications/Instructions

HTY7903

HTY7913

Содержание HTY79

Страница 1: ...ensing only dewpoint temperature without separate temperature sensor is also available Features 1 Wide sensing range 2 Excellent long term stability 3 Highly resistant to environment 4 Quick response and high repeatability 5 Easy to install in a duct bracket prepared 6 Splash proof housing IP54 Models Model No Shape Type Power supply Humidity output Temperature output Fixed Fixed Description HTY79...

Страница 2: ...for reference at any time Usage Restrictions This product is targeted for general air conditioning Do not use this product in a situation where human life may be affected If this product is used in clean rooms or places where reliability or control accuracy is particularly required please contact Yamatake s sales representatives Yamatake Building Systems Co Ltd bears no responsibility for any bene...

Страница 3: ...Yseries Power consumption 0 6 VA at conditions of 24 V AC HTY HY series 1 5 V 0 10 V output model 450 mW at conditions of 24 V DC HTY HY series 1 5 V 0 10 V output model 1 4 VA at conditions of 24 V AC HTY HY series 4 20 mA output model 1 2 W at conditions of 24 V DC HTY HY series 4 20 mA output model Dielectric strength 500 VAC less than 1 mA of leak for 1 minute Insulation resistance 500 VDC min...

Страница 4: ...4 AB 5963 Dimensions mm 1 7903 series 2 7913 series 3 Mounting bracket 62 5 25 50 60 40 60 72 3 φ30 3 3 247 6 51 3 45 6 67 3 A 70 φ20 110 1135 A 108 6 51 3 45 6 67 3 70 φ20 110 1135 ...

Страница 5: ...t the point indicated on the label Fix the mounting bracket onto the duct with M4 screws inserting packing between the duct and the bracket Cover the duct with an insulating material If you cover the duct with an insulating material first fill the clearance between the bracket and the duct with the insulating material after fixing the bracket 2 Turn the stopper of the main unit to the left and ins...

Страница 6: ...e conduit at a point where the conduit lock screw can be tightened easily 2 Connect the wires to the terminals and close the cover Tighten the seal connector only when cable connected Terminal Nos and cable cores Seal connector order separately Nut attached to conduit Attachment Conduit connector nominal size 25 mm Pull the cable Tightening direction Nut attached to conduit Conduit connector nomin...

Страница 7: ... generating noise due to inadequate time constant of the controller input Use a controller with a low pass filter with a removal ratio of 40 dB or higher normal mode Connect an isolator to the controller input circuit if a removal ratio is unknown If you use a Yamatake cotnroller no problem will occur Maintenance Since the temperature humidity sensor have been in spected and adjusted accurately be...

Страница 8: ...d The out put value is increased by turning this volume in clock wise direction and decreased by turning it counter clockwise Use refelenced humidity meter of ade quate accuracy A digital multimeter is recommend ed to check the output voltage Parts Identification of adjustment volume Cautions 1 After unpacking age the transmitter in the ambient atmosphere for at last 24 hours 2 To calibrate and ad...