3
Product and functional description
09.2019
19
ba
-o
.4
.1
.3
-en
-2
.2
-y
3.7.6
Signaling relays
CAUTION
The signalling relays
“
err
”
and "
option
" are used to output error messages and may
not
be used for safety-relevant functions.
The signalling relays may only be parameterised by an
electrically skilled person
.
Both relays can be parameterised as normally-closed or normally-open contacts:
Relay
Normally-open Normally-closed
option
S3_7 off
S3_7 on
err
S3_6 off
S3_6 on
err
is switched in every error state that stops a
lifting movement
.
option
is freely parameterisable. Parameterisation is dependent on the switch position
S3:
DIP switch:
Switch
S3_3
Switch
S3_4
Switch
S3_5
The option relay
0
0
0
does not switch
1
0
0
switches on overload
0
1
0
switches on overheating
1
1
0
switches on sensor error
0
0
1
switches on all errors that prohibit lifting and lowering
1
0
1
Switch-off pulse on overload: option relay switches
off for 500 ms and then on again
0
1
1
switches at 95 % of nominal load
1
1
1
not used
The settings are made during initial commissioning in the factory.