PolluFlow

1. General

This guide is intended for trained specialized personnel. For this reason no basic working 

steps are included. Observe the instructions for the use of flow sensors!

The installation must only be carried out by a specialist installation or electrical company. 

The personnel must be trained in the installation and handling of electrical equipment and be 

cog- nisant of the Low Voltage Directive.

Please note that the connection threads may be sharp-edged. We therefore recommend to 

wear protection gloves.

The relevant ESD regulations (electrostatic discharge) must be observed. No responsibility 

is accepted for damage (especially to the elec- tronics), resulting from non-observation of 

the rules.

The tamper-evident seal on the flow sensor must not be broken! A damaged seal will 

result in immediate invalidation of the fac- tory warranty and verification. The cables 

supplied  with  the  meter  must  neither  be  shortened,  extended  nor  changed  in  any 

other way.

Medium

Water according to CEN Recommendation CEN/TR 16911 (the lifecycle of the meter may be 

impaired if not observed).

Temperature range

The temperature range is dependent on the variant and nominal size (see type plate).

Pipeline insulation

In the case of the pipeline insulation, the housing with the elec- tronics must remain free (see 

Fig. 

3

). Otherwise the electronic will run too hot and could be damaged.

Further details about the variants and the applicable standard EN1434-6 can be found in the 

data sheet. These must be observed without fail. The data sheet is available under www.

sensus.com 

2. Installation

The unit you have purchased contains electronic components which could be destroyed by 

electric or magnetic fields. For this reason, neither the device itself nor the incoming and 

outgoing cables must be installed in the immediate vicinity of heavy elec- trical loads or their 

conduits (e.g. switches, electric motors). The precise separation depends on the magnitude 

of the voltage and current in these consumers. In case of doubt consult an expert.

• 

The flow sensor must be fitted in either a hot or cold pipe of the system. Ensure that the 

flow sensor is mounted in the mounting position corresponding to the temperature of the 

medium (see "6. Temperature loads" and Fig. 

1

).

• 

The flow sensor must be installed so that the flow direction matches the arrow direction 

on the sensor.

• 

Calming  sections  are  not  necessary  before  and  after  the  flow  sensor,  but  calming 

sections of 3...10 DN are recommended before the meter. 

  

Installation in both horizontal and vertical pipe sections is possible, however must never be 

such that air bubbles can collect in the meter (see Fig. 

2

). The flow sensor must always be 

filled with liquid. Avoid frost at the meter. We recommend installing the flow sensor in a tilted 

position (approx. 45°).

It is recommended that shut-off valves are fitted upstream and downstream of the flow sensor 

to simplify its demounting. When demounting, an open-ended spanner must be used on the 

bottom of the sensor (see Fig. 

4

).

3. Power supply

3.1 External power supply (e.g. via meter electronics)

•  Power supply 3.0 … 5.5 VDC

• 

Power consumption < 100 mAh per year

• 

Pulse current < 10 mA

4. Connection diagram

The function of the individual coloured cables are shown in the following illustrations.

Damages or failure of the meter can occur, if the cables are reversed or wrongly connected. 

4.1 Connection to the calculator

Please make sure that the calculator and flow sensor have the same pulse value marking. 

With a junction box (order number: 88599001) the pulse cable can be extended up to 10 

m by extending the pulse cble with a shielded cable with at least two strands (e.g. I-Y(St)Y 

2x2x0,8).

At the PolluTherm calculator terminal 10 and 11 are used for the pulse input. Terminal 9 is 

for the power supply. During the connection of the cable the polarity needs to be respected.

 

4.2 External power supply 3.0 – 5.5 V

5. Communication

The flow sensor has two pulse outputs for connection to a heat meter.

•  Useful pulse

•  Test pulse (high resolution for testing laboratories)

The electrical data of the useful pulse are defined as:

Designation

Value

External power supply

UC < 30 V

Output current

< 20 mA with a residual voltage of < 0.5 V

Open Collector (drain)
Cable length to the partial unit energy 

meter

< 10 m

Output frequency battery supplied

< 20 Hz

Output frequency with external power

supply

< 150 Hz

Useful pulse value

1 l and 10 l (dependent on the nominal size)

Pulse duration

100 ms ± 10 %;

Pulse duration < Pulse pause

Potential free contact (optional)

 

6. Temperature loads

Operating / ambient conditions

•  Standard: 5 … 55 °C; IP 54; 93 % rel. humidity

•  Sealed: 5 … 55 °C; IP 65; 93 % rel. humidity

Media temperatures

Configuration

Temperature range

Heat - externally supplied

q

p

 0.6 ... 2.5 m³/h: 5 ... 130 °C

q

p

 3.5 ... 60 m³/h: 5 ... 150 °C

Cold - externally supplied

5 ... 120 °C

Note that in heat applications, the water temperature must be greater than the ambient 

temperature.Once commissioned, avoid frost at the meter.

7. Environnmental conditions

•  Electromagnetic enviornmental conditions: Class E2

•  Mechanical enviornmental conditions: Class M2

Use standard flow sensors:

•  at water temperatures permanently above ambient temperatures

Use potted flow sensors:

•  For cold applications or T

water

 < 

Tambient

•  If permanent condensation is expected

8. 

Environmental note

The device shall not be disposed together with the domestic waste. 

Test pulse

Volume pulse

PolluFlow

+ 3 ... 5 V

brown
yellow

white

blue

GND

Ultrasonic flow sensor

2

3

1

4

- 2 -

EN

DE

FR

ES

CZ

SK

PL

RU

ENGLISH

q

p

 0.6 - 2.5: 5 ... 130 °C

q

p

 3.5 - 60: 150 °C

q

p

 0.6 - 2.5: 5 ... 130 °C

q

p

 3.5 - 60: 150 °C

q

p

 0.6 - 60: 5 ... 130 °C

Содержание SENSUS PolluFlow

Страница 1: ...Installation guide Einbauanleitung Guide d installation Instrucciones de instalaci n N vod na mont a obsluhu N vod na mont a obsluhu Instrukcja monta u PolluFlow...

Страница 2: ...must always be filled with liquid Avoid frost at the meter We recommend installing the flow sensor in a tilted position approx 45 It is recommended that shut off valves are fitted upstream and downst...

Страница 3: ...9 Declaration of conformity for MID meters EN DE FR ES CZ SK PL RU...

Страница 4: ...rdings nie so dass sich Luftblasen im Z hler ansammeln k nnen siehe Abb 2 Der Durchflusssensor muss immer mit Fl ssigkeit gef llt sein Frost am Z hler ist zu vermeiden Wir empfehlen den Durchflusssens...

Страница 5: ...9 Konformit tserkl rung f r Ger te nach MID EN DE FR ES CZ SK PL RU...

Страница 6: ...dons l installation du capteur de d bit dans une position inclin e env 45 Afin de faciliter le d montage du capteur de d bit il est conseill de mettre en place des vannes d arr t en amont et en aval d...

Страница 7: ...9 D claration de conformit pour les appareils conformes MID EN DE FR ES CZ SK PL RU...

Страница 8: ...en el medidor ver Fig 2 El sensor de flujo siempre debe estar lleno con un l quido Evitar congelaci n en el medidor Se recomienda la instalaci n del sensor de flujo en una posici n inclinada aprox 45...

Страница 9: ...9 Declaraci n de conformidad para medidores MID EN DE FR ES CZ SK PL RU...

Страница 10: ...n poloze P ibli n 45 Doporu ujeme instalaci uzav rac ch ventil p ed a za sn ma em pr toku aby se zjednodu ila jeho demont P i demont i mus b t na spodn stran senzoru pou it otev en kl viz obr 4 3 Zdr...

Страница 11: ...9 Prohl en o shod pro m i e MID EN DE FR ES CZ SK PL RU...

Страница 12: ...ovolen vystavi prietokomer p sobeniu mrazu V robca doporu uje mont v ikmej polohe pribli ne 45 Pre zjednodu enie pr c pri demont i a op tovnej mont i je doporu en osadi pred a aj za prietokomerom uzat...

Страница 13: ...9 Prehl senie o zhode pre MID meradl EN DE FR ES CZ SK PL RU...

Страница 14: ...y unika zamarzni cia urz dzenia Zaleca si montowa przetwornik przep ywu w po o eniu przechylonym ok 45 Zaleca si aby w celu uproszczenia demonta u urz dzenia przed i za przetwornikiem przep ywu by y z...

Страница 15: ...9 Deklaracja zgodno ci dla urz dze pomiarowych z MID EN DE FR ES CZ SK PL RU...

Страница 16: ...I Y St Y 2x2x0 8 88599001 PolluTherm 10 11 9 4 2 3 0 5 5 5 UC 30 B 20 0 5 10 20 150 1 10 100 10 6 5 55 C IP 54 93 5 55 C IP 65 93 qp 0 6 2 5 5 130 C qp 3 5 60 5 150 C 5 120 C 7 E2 M2 T 8 pulse PolluF...

Страница 17: ...A 20020 Lainate MI Italy 39 02 61291861 info it xyleminc com Sensus Polska Sp z o o ul Mazowiecka 63 65 PL 87 100 Torun Poland 48 56 654 3303 info pl xyleminc com Sensus esk Republika spol s r o Ol an...

Отзывы: