INSTRUCTION MANUAL 

MM-243D

2

Approximate

Distance Above

Cast Line

Differential

Setting

In.   (mm)

In.   (mm)

Pump Off

1

3

/

8

(35)

3

/

4

(19)

Pump On

5

/

8

(16)

Burner On

7

/

8

(22)

7

/

8

(22)

Burner Off

0

(0)

NORMAL BOILER

WATER LINE

PUMP

OFF

BURNER

OFF

BURNER

“CUT-OFF LEVEL” 

AT CAST LINE

1 3/8" (35mm)

CUT-OFF 

LEVEL

NORMAL BOILER

WATER LINE

CUT-OFF 

LEVEL

PUMP OFF
PUMP ON

3/4" (19mm)

OPERATION

Maximum Pressure:

50 psi (3.5 kg/cm

2

)

Electrical Ratings

Settings and Differential Pressures

Values are ±

8

” (3.2mm).

Series 42S

50 psi

(3.5 kg/

cm

2

)

Pressure

Pump Circuit Rating (Amperes)

Voltage

Full Load

Locked Rotor

Pilot Duty

120 VAC

7.4

44.4

345 VA at

240 VAC

3.7

22.2

120 or 240 VAC

NORMAL BOILER

WATER LINE

BURNER

CUT-OFF LEVEL 

AT CAST LINE

7/8" (22 mm)

BURNER ON
BURNER OFF

CUT-OFF 

LEVEL

Motor Horsepower

Voltage

Hp

120 VAC

1/3

240 VAC

1/3

• Before using this product read and understand instructions.

• Save these instructions for future reference.

• All work must be performed by qualified personnel trained in the proper application, instal-

lation, and maintenance of plumbing, steam, and electrical equipment and/or systems in 
accordance with all applicable codes and ordinances.

• To prevent serious burns, the boiler must be cooled to 80˚F (27˚C) and the pressure must be

0 psi (0 bar) before servicing.

• To prevent electrical shock, turn off the electrical power before making electrical connections.

• This low water cut-off must be installed in series with all other limit and operating controls 

installed on the boiler. After installation, check for proper operation of all of the limit and 
operating controls, before leaving the site.

• To prevent serious personal injury from steam blow down, connect a drain pipe to the

control opening to avoid exposure to steam discharge.

• To prevent a fire, do not use this low water cut-off to switch currents over 7.4A, 1/3 Hp at

120 VAC or 3.7A, 1/3 Hp at 240 VAC, unless a starter or relay is used in conjunction with it.

Failure to follow this warning could cause property damage, personal injury or death.

WAR

NING

CAUT

ION

!

WARNING

Replacement Head Mechanism

Replacement head mechanisms can be installed without
disturbing existing equalizing connections or disassembly
of components, making repairs simple and easy.

Replacement Head Mechanism

42S-HD

(Snap Switch)

Содержание McDonnell & Miller MM-243D

Страница 1: ...l other limit and operating controls installed on the boiler After installation check for proper operation of all of the limit and operating controls before leaving the site To prevent serious persona...

Страница 2: ...ems in accordance with all applicable codes and ordinances To prevent serious burns the boiler must be cooled to 80 F 27 C and the pressure must be 0 psi 0 bar before servicing To prevent electrical s...

Страница 3: ...w the boiler to cool to 80 F 27 C and release the boiler pressure to 0 psi 0 bar b Using a flathead screwdriver remove the junction box cover B Disconnect mark and remove the supply wires and conduit...

Страница 4: ...w the boiler to cool to 80 F 27 C and release the boiler pressure to 0 psi 0 bar b Using a flathead screwdriver remove the junction box cover B Disconnect mark and remove the supply wires and conduit...

Страница 5: ...unction box cover B 5 B STEP 3 Electrical Wiring a Using a flathead screwdriver remove the junction box cover B b Following the appropriate wiring diagram refer to page 6 based on your application req...

Страница 6: ...attach the junction box cover B 5 B STEP 3 Electrical Wiring a Using a flathead screwdriver remove the junction box cover B b Following the appropriate wiring diagram refer to page 6 based on your app...

Страница 7: ...m steam pipe blow down connect a drain pipe to the control opening to avoid exposure to steam discharge Failure to follow this caution could cause personal injury CAUTION NOTE More frequent blow down...

Страница 8: ...e blow down system for each control Blow down the control when the water in the boiler is at its normal level and the burner is on NOTE Refer to page 2 for switch operating points Open upper valve 1 S...

Отзывы: