en - Original instructions
52
alarm for
minimum
pressure
threshold
(only for
system with
sensor)
bled
1= Enabled
r54
Setting the
minimum
pressure
threshold
0 to Full
scale sen-
sor
(0= disa-
bled)
Vari-
ous
0
t54
Delay time
until activa-
tion of min-
imum pres-
sure alarm
threshold
(c54=1)
0 to 200
sec
20
c55
Enable
alarm for
maximum
pressure
threshold
alarm (only
for system
with sensor)
0= Disa-
bled
1= Enabled
-
0
r55
Setting the
maximum
pressure
threshold
alarm. All
pumps are
stopped in
case of
alarm
0 to Full
scale sen-
sor
(0= disa-
bled)
Vari-
ous
0
t55
Delay time
until activa-
tion of max-
imum pres-
sure alarm
threshold
(c55=1)
0 to 200
sec
0
SETTING SYSTEM ALARM BLOCK
c56
Enables
system
block if the
same alarm
occurs five
times in 30
min. A man-
ual reset is
necessary to
restart the
system.
0= Disa-
bled
1= Enabled
-
0
c57
Reset the
alarm log
0= No
1= Yes
-
0
(1) D IN PROG=1 is set
(Minimum pressure out of operation range is detected)
If the pressure switch is activated in automatic mode
and not during Auto-test, the following happens:
- If the pumps are running they will not be
stopped and alarm A38 will be shown.
- If the pumps are not running they will not start
and alarm A38 will be shown. If there is a pres-
sure drop, however, they will be switched on
and alarm A38 continues to be shown.
If the minimum pressure is activated during the
Auto-test, see section
8
SPECIAL FUNCTION
BOOSTER APPLICATION (parameter bS is se-
lected, see section
8.1
Auto-test RUN
Using the Auto-test function, the pumps can be
switched ON when they have been OFF for a long
time.
The pumps are switched ON by the clock or by an
external digital contact (c24).
NOTICE:
The following components have to be used:
•
Solenoid valve: it is required to drain the water
during the test.
•
Membrane pressure switch or equivalent de-
vice. It is used to check the performance of the
pump to prevent its value from dropping too
low. It is connected to D IN PROGR of the Q-
SMART control panel (refer to figures
•
Q-SMART-6FVC MODULE, electronic card
relay voltage-free contacts (refer to figures
How to start the auto-test: activation by clock
(c24=1)
If the pumps are running, the auto-test is put on
hold and this text is shown on the display in blink-
ing mode:
When the pumps are in standby, the auto-test
starts and the test in progress and the pump in use
are shown on the display in blinking mode:
How to stop the auto-test
The auto-test can be stopped at any time by press-
ing the OK button.
What does the Auto-test Run do?
tSt
tSt
P1
Содержание Lowara Q-smart
Страница 2: ......
Страница 239: ...el 239 Tab 1 4 4 1 o 30 mA RCD o 3 mm C F1 F2 12 gG 7 5 4 3 5 4 4 3 2 70 C 158 F 4 2 4...
Страница 255: ...el 255 A54 r54 t54 o o o Reset A55 r55 t55 c02 0 t55 c02 1 o o o Reset A56 5 30 5 30 c57...
Страница 266: ...el 266...
Страница 298: ...ru 298 2 3 4 3 4 1 4 4 1 o 30 o 3 C 12 A gG F1 F2 7 5 4 3 5 4 4 3 2 70 C 158 F 4 2 4...
Страница 326: ...ru 326 o sE 2 o bS 3 11 11 1 2 Q SMART 30 12 7 9 12 1 F1 F2...
Страница 327: ...ru 327...
Страница 347: ...347 Q SMART 30 RCD 12 7 9 12 1 on F1 F2...
Страница 351: ...it en fr de es pt nl pl el tr ru ar 351 5 INST QSMARTCAVI_G_22_A SC 2 3 4 5 6 1...