82
0600 0600 SUBMENU ERRORS
0605
0605 MIN. THRESH.
disabled
minimum threshold limit
Possible settings:
disabled - max. SENSOR RANGE
•
An adjusted value >0.00 has to be reached within the programmed DELAY TIME [0610]
•
If this value can’t be reached, the HYDROVAR stops with the failure message MIN.
THRESHOLD ERROR.
•
To disable the minimum threshold limit, press
▼
till disabled is shown on the display.
0610
0610 DELAY - TIME
2 Sec
minimum threshold limit delay time
Possible settings:
1 – 100 sec
Delay time to switch-off the HYDROVAR in case the actual value drops below the min.
threshold limit or a connected external low water protection at terminals X3/11-12 has
been opened.
Notice:
The min. threshold function is also active during start up of the pump!
Therefore the delay time has to be set higher than the duration that is needed, to reach a
value above the limit.
0615
0615 ERROR RESET
ON
Automatic error reset
Possible settings:
ON – OFF
ON:
Allows an automatic restart for 5 times in case of a failure. If the failure is still active
after the 5
th
restart, the HYDROVAR will shut off and the appropriate error message is
shown.
The internal counter of the automatic error reset is decreased by 1 after each operating
hour, so if an error could be reset after 3 restarts, there are 3 further restarts possible after
one hour, 4 after two hours and 5 automatic restarts after 3 operating hours.
A manual reset can be done by switching an external ON/OFF (X3/7-8) contactor.
Not each error can be reset automatically.
(For detailed information see chapter 11 failure messages)
OFF:
if the ERROR RESET is set to OFF, each failure would be shown on the display directly
and must be reset manually.