Parameter
Description
Range
Unit
Default
Minimum Pressure Setting
- an
A4
alarm (Minimum
Pressure) is triggered when
the system pressure drops
below the
value for
longer than the time set in
dL
(Minimum Pressure
Delay Timer). When the
alarm is triggered, the
pump stops and the ART
function is enabled. See
Set to 0.0 to disable.
0.0–(
SP
-6.0)
0.0: Disabled
PSI
0.0
dL
Minimum Pressure Delay
Timer – delay timer for
triggering of the
A4
(Minimum Pressure)
alarm.
0–99
sec
20
rS
Reverse Motor Rotation -
For RB3 models, reverse
the direction of motor
rotation.
0=no action
1=reverse the direction of
rotation
0–1
-
0
dP
Pressure Drop - This
parameter is the value for
starting the pump after a
stop, calculated as a
percentage of the Pressure
Setpoint (
SP
) value.
For example:
SP
= 60 psi
dP
= 90 %
The controller will restart
the pump when the
pressure drops below 54
psi.
0–99
%
90
5 System Description
ResiBoost INSTRUCTION MANUAL
21