![Xylem Bell & Gossett e-80SCXL Series Скачать руководство пользователя страница 21](http://html1.mh-extra.com/html/xylem/bell-and-gossett-e-80scxl-series/bell-and-gossett-e-80scxl-series_instruction-manual_3909941021.webp)
5.2 Prime the pump
CAUTION:
Do not run the pump dry.
Make sure that the pump body is full of liquid before startup. If the system does not
automatically fill the pump body with liquid, then you must manually prime the pump.
1. Loosen the vent plugs on the pump body. Loosen the vent valve on the flush line
assembly.
2. While venting the air from the pump body, rotate the pump shaft a few times by hand.
3. After all air has been purged from the pump, close the vent plugs.
5.3 Start the pump
CAUTION:
• Observe the pump for vibration levels, bearing temperature, and excessive noise. If
normal levels are exceeded, shut down the pump and resolve the issue.
Before you start the pump, you must perform these tasks:
• Open the suction valve.
• Open any recirculation or cooling lines.
1. Fully close or partially open the discharge valve, depending on system conditions.
2. Start the driver.
3. Slowly open the discharge valve until the pump reaches the desired flow.
4. Immediately check the pressure gauge to ensure that the pump quickly reaches the
correct discharge pressure.
5. If the pump fails to reach the correct pressure, perform these steps:
a) Stop the driver.
b) Prime the pump again.
c) Restart the driver.
6. Monitor the pump while it is operating:
a) Check the pump for bearing temperature, excessive vibration, and noise.
b) If the pump exceeds normal levels, then shut down the pump immediately and correct
the problem.
7. Repeat steps 5 and 6 until the pump runs properly.
5.4 Pump operation precautions
General considerations
CAUTION:
• Vary the capacity with the regulating valve in the discharge line. Never throttle the flow
from the suction side since this can result in decreased performance, unexpected heat
generation, and equipment damage.
• Do not overload the driver. Driver overload can result in unexpected heat generation and
equipment damage. The driver can overload in these circumstances:
– The specific gravity of the pumped fluid is greater than expected.
– The pumped fluid exceeds the rated flow rate.
• Make sure to operate the pump at or near the rated conditions. Failure to do so can result
in pump damage from cavitation or recirculation.