TESTING

Inspection before use

Trial

o

Check installation of the whole machine and the pipe connections according to the

 

pipe

connection diagram

o

Check the electric wiring according to the electric wiring diagram; and make sure the Heat

 

Pump is

bonded

o

Make sure that the main machine power switch is off

o

Check the temperature setting.

o

Check the air inlet and outlet.

The user must “Start the Pump before the Machine, And Turn off the Machine

 

before the

Pump”, or the machine will be damaged

The user should start the pump, check for any water leakage of water; set

 

temperature

in the thermostat, and then switch on power supply.

In order to protect the swimming pool heat pump, the machine is equipped with a

 

time delay

starting  function,  when  starting  the  machine,  the  blower  will  run  for  3

 

minutes  before  the

compressor starts.

If  at  any  time  there  is  an  abnormal  noise,  smell,  smoke,  electricity  leakage,  please

 

switch  off

 

power

immediately and contact your local dealer.

Attention

o

Set  temperature  control  to  achieve  a  comfortable  water  temperature  and  to  avoid

 

overheating  or

over

 

cooling.

o

Always install the machine outdoors, while noting the minimal clearances needed for

 

proper operation

and

 

heating. DO NOT place the unit next to shrubs, fences, etc.

 

which can block the air inlet. These

locations

 

deny the unit a continuous source of

 

fresh air which reduces its efficiency and may prevent

adequate heat

 

delivery.

o

Never put hands or any objects into outlet of the swimming pool heat pump, and don’t

 

remove the screen

over the fan at any time.

o

If at any time there is an abnormal noise, odor, smoke, electricity leakage, please

 

switch off power

immediately and contact your local dealer.

o

Do not use or stock combustible gas or liquids such as paint thinners, paint, fuel near

 

or around the heat

pump.

o

As with all pool heat pumps, you are advised to use a pool cover at night and when

 

the pool is not in

use.

o

The heat pump should be installed within 10m of the pool to minimize heat loss in

 

the underground

pipes.

Safety

Please keep the main power supply switch out of reach from children.

o

If  there 

is a power outage while the machine is in operation, the heat pump will start

 

up automatically

when power is restored.

o

Please switch off the main power supply during lightening storms to prevent any

 

damage to the unit.

o

If the machine is stopped for a long time, please cut off the power supply and drain

 

water of the machine

by opening the tap of inlet pipe. If the unit is stopped for a long

 

period of time or for winterizing, the unit

must be drained of all its water. You will need

 

to disconnect the IN and OUT water connections. Then the

unit must be tilted or

 

blown out with air until all water is out.

Содержание 75217

Страница 1: ...UAL KEEP THIS MANUAL FOR SAFETY WARNINGS PRECAUTIONS ASSEMBLY OPERATION INSPECTION MAINTENANCE AND CLEANING PROCEDURES WRITE THE PRODUCT S SERIAL NUMBER ON THE BACK OF THE MANUAL OR THE MONTH AND YEAR...

Страница 2: ...eeded for proper operation and heating DO NOT place the unit next to shrubs fences etc which can block the air inlet These locations deny the unit a continuous source of fresh air which reduces its ef...

Страница 3: ...2 Note There may be variations in values due to climatic conditions...

Страница 4: ...or Water Piping Connections Note The diagram is for demonstration purposes only and layout of the pipes is for reference only Electric Wiring Diagram Note The swimming pool heat pump must be grounded...

Страница 5: ...98 inches should be allowed on the air outlet side for unrestricted air discharge The unit must not be installed under a porch Any other side of the unit should be located at least 28 inches from a wa...

Страница 6: ...our dealer for service Wiring 1 The wiring of your pool heat pump should be performed by a qualified electrician in accordance with local requirements A properly sized breaker and copper wire must be...

Страница 7: ...on is maintained in the parameter interface If the heat pump is running press 3S to check parameter but can t change parameters NO Meaning Range Change Factory setting P01 Cooling setting water temper...

Страница 8: ...Press button 3S to enter check system current status interface NO Meaning Range Remarks A01 Water temperature 4 210 F Measured value A02 Compressor Exhaust temperature 4 257 F Measured value A03 Heat...

Страница 9: ...he or keys Press botton again to change the minutes using the or keys Press botton the time displayed and 1 OFF to blink Change the hour using the or keys Press botton again to change the minutes usin...

Страница 10: ...which can block the air inlet These locations deny the unit a continuous source of fresh air which reduces its efficiency and may prevent adequate heat delivery o Never put hands or any objects into o...

Страница 11: ...its water You will need to disconnect the IN and OUT water connections Then the unit must be tilted or blown out with air until all water is out iii Please clean this machine with household detergents...

Страница 12: ...ure setting set too high Check and repair E05 High pressure protection Insufficient water flow Check the water flow Pressure switch out of order Replace the pressure switch Have Too much refrigerant g...

Страница 13: ...12...

Страница 14: ...T PARTSTHERETO ORARISING OUT OFHISORHER INSTALLATION OFREPLACEMENT PARTS THERETO Record Product s Serial Number Here ___________________ Note If product has no serial number record month and year of p...

Отзывы: