17
Interface
Setting
Parameter 2:
Set up the charger maximum current.
1/2/4/6/8:
setting the charger maximum current
1/2/4/6/8 in Ampere. (Default: 4A)
Recharge time VS charging current is as below table.
Unit: hours
1500VA
2000VA 3000VA
8A
0.7
1.4
1.1
6A
0.9
1.9
1.4
4A
1.4
2.9
2.1
2A
2.8
5.7
4.2
1A
5.6
11.4
8.5
⚫
16: EPO logic setting
Interface
Setting
Parameter 2:
Set up the EPO function control logic.
AO:
Active Open (Default). When AO is selected as EPO
logic, it will activate EPO function with Pin 1 and Pin 2 in
open status.
AC:
Active Close. When AC is selected as EPO logic, it will
activate EPO function with Pin 1 and Pin 2 in close status.
⚫
17: Site fault detection enable/disable
Interface
Setting
Parameter 2:
Enable or disable site fault detection. You
may choose the following two options:
ENA:
Site fault detection enable(Default for 120 models)
DIS:
Site fault detection disable(Default for 230 models)
⚫
18: Display setting for autonomy time
Interface
Setting
Parameter 2:
Set up the display setting for autonomy time
EAT:
If EAT is selected, it will display the remaining
autonomy time. (Default)
RAT:
If RAT is selected, it will show accumulated autonomy
time so far.
⚫
00: Exit setting
Interface
Setting
Exit the setting mode.