15
⚫
04: ECO enable/disable
Interface
Setting
Parameter 2:
Enable or disable ECO function. You may
choose the following two options:
ENA:
ECO mode enable
DIS:
ECO mode disable (Default)
⚫
05: ECO voltage range setting
Interface
Setting
Parameter 2:
Set the acceptable high voltage point and
low voltage point for ECO mode by pressing Down key or Up
key.
HLS:
High loss voltage in ECO mode
in parameter 2.
For 230 Models,
the setting range in parameter 3 is from +7V
to +24V of the nominal voltage. (Default: +12V)
For 120 Models,
the setting range in parameter 3 is from +3V
to +12V of the nominal voltage.
(Default: +6V)
LLS:
Low loss voltage in ECO mode in parameter 2.
For 230 Models,
the setting range in parameter 3 is from -7V
to -24V of the nominal voltage.
(Default: -12V)
For 120 Models,
the setting voltage in parameter 3 is from -3V
to -12V of the nominal voltage.
(Default: -6V)
⚫
06: Bypass enable/disable when UPS is off
Interface
Setting
Parameter 2:
Enable or disable Bypass function. You may
choose the following two options:
ENA:
Bypass enable
DIS:
Bypass disable (Default)
⚫
07: Bypass voltage range setting
Interface
Setting
Parameter 2:
Set the acceptable high voltage point and
acceptable low voltage point for Bypass mode by pressing
the Down key or Up key.
HLS:
Bypass high voltage point
For 230 Models
:
230-264:
setting the high voltage point in parameter 3
from 230Vac to 264Vac. (Default: 264Vac)
For 120 Models
:
120-140:
setting the high voltage point in parameter 3
from 120Vac to 140Vac. (Default: 132Vac)
LLS:
Bypass low voltage point
For 230 Models
:
170-220:
setting the low voltage point in parameter 3 from
170Vac to 220Vac. (Default: 170Vac)