background image

Xtreme Power Conversion Corporation

E91 User’s Manual

Page 49

Uninterruptible Power Supply

4. Trouble Shooting

Symptom

Possible cause

Remedy

No indication and alarm in the 

front display panel even though the 

mains is normal. 

The AC input power is not con

-

nected well.

Check if input cable firmly connect

-

ed to the mains. 

The warning code 0B.

EPO function is activated. At this 

time, the EPO switch is in “OFF” 

status or the jumper is open.

Set the circuit in closed position to 

disable the EPO function. 

The warning code 01.

The external or internal battery is 

incorrectly connected.

Check if all batteries are connected 

well.

The warning code 09.

UPS is overload. 

Remove excess loads from UPS 

output.

UPS is overloaded. Devices con

-

nected to the UPS are fed directly 

by the electrical network via the 

Bypass.

Remove excess loads from UPS 

output.

After repetitive overloads, the UPS 

is locked in the Bypass mode. Con

-

nected devices are fed directly by 

the mains.

Remove excess loads from UPS out

-

put first. Then shut down the UPS 

and restart it.

Fault code is shown as 43. 

UPS is overload too long and be

-

comes fault. Then UPS shut down 

automatically.

Remove excess loads from UPS 

output and restart it.

Fault code is shown as 14, 15, 16, 

17, 18 or 19, 

The UPS shut down automatically 

because short circuit occurs on the 

UPS output.

Check output wiring and if con

-

nected devices are in short circuit 

status.

Other fault codes are shown on 

LCD display and alarm beeps con

-

tinuously.

A UPS internal fault has occurred. 

Contact your dealer

Battery backup time is shorter than 

nominal value.

Batteries are not fully charged.

Charge the batteries for at least 7 

hours and then check capacity. If 

the problem still persists, consult 

your dealer. 

Batteries defect

Contact your dealer to replace the 

battery.

The warning code 0A.

Fan is locked or not working. Or the 

UPS temperature is too high.

Check fans and notify dealer. 

The warning code 02.

The input neutral wire is discon

-

nected.

Check and correct the input neutral 

connection. If the connection is ok 

and the warning is still displaying, 

please check input fuses of S and T.

The S or T input fuse is broken.

Replace the fuse.

Содержание E91

Страница 1: ...E91 Online UPS 10kVA 15kVA 20kVA 30kVA 40kVA Models User Installation Manual www xpcc com 2022 Xtreme Power Conversion Corporation All rights reserved Rev 3 25 22...

Страница 2: ...G AND INSPECTION 6 2 2 UPS FLOOR ANCHORING 6 2 3 WIRING TERMINAL VIEW 7 2 4 OPERATION PRINCIPLE 9 2 5 SINGLEUPSINSTALLATION 9 2 6 UPSINSTALLATIONFORPARALLELSYSTEM 12 2 7 SOFTWARE INSTALLATION 14 3 OPE...

Страница 3: ...heat source Do not block ventilation holes on the UPS housing 1 3 Installation Do not connect appliances or devices which would overload the UPS e g big motor type equipment to the UPS output termina...

Страница 4: ...electrical maintenance personnel of the presence of a UPS in the circuit The label will bear the following or an equivalent text Before working on this circuit Isolate Uninterruptible Power Supply UP...

Страница 5: ...be operated by any individuals with no previous experience 1 6 Standards Safety UL 1778 CSA C22 2 No 107 3 14 EMI Conducted Emission FCC Part 15 Subpart B Class A Radiated Emission FCC Part 15 Subpart...

Страница 6: ...parallel cable option One shared current cable option NOTE Before the installation please inspect the unit Be sure that there is no physical damage to the unit Do not turn on the unit and notify the...

Страница 7: ...poration E91 User s Manual Page 7 Uninterruptible Power Supply 2 3 Wiring Terminal View E91 units with internal batteries E91 10K Rear Panel E91 15K 20K Rear Panel E91 10K Input Output Terminal E91 15...

Страница 8: ...sion Corporation E91 User s Manual Page 8 Uninterruptible Power Supply E91 units with internal batteries E91 30 40K front view door removed E91 30 40K rear view E91 30 40K wiring panels E91 30 40k cab...

Страница 9: ...normal operation To activate EPO function please remove the jumper 4 Share current port 5 Parallel port 6 Intelligent slot 7 External battery connector 8 Line input circuit breaker switch 9 Maintenanc...

Страница 10: ...the mains switch in the building before installation 3 Turn off all the connected devices before connecting to the UPS 4 Prepare wires based on the following table CAUTION To reduce the risk of fire...

Страница 11: ...s Connect the grounding earthing wire first when making other wire connections Re move the grounding earthing wire last when connecting the UPS NOTE For single utility power system connect input termi...

Страница 12: ...40K Battery connection wiring NOTE 1 Make sure that the wires are connected securely with the terminals NOTE 2 Please install the output breaker between the output terminal and the load and the break...

Страница 13: ...onnection with wrong battery voltage may cause irreversible damage of the UPS Pay special attention to the polarity marking on external battery terminal block Connection with wrong battery voltage may...

Страница 14: ...l system for 30K 40K 6 Refer to the following communication wiring diagrams for share current cable and parallel cable connections Diagram 1 Two UPSs in parallel Diagram 2 Three UPS in parallel Parall...

Страница 15: ...s the button to set up the power supply for the UPS UPS will enter to power on mode After initialization UPS will enter to No Output mode 3 2 LED Indicators and LCD Panel LED Indicators There are 4 LE...

Страница 16: ...WORD INSTALL INFO VOL CALI CURR CALI INITIAL ELECTRICAL BATTERY MISCELLANEOUS UPS SELFTEST ELECTRICAL BATTERY MISCELLANEOUS PAS SWORD 0000 PARAMETER INFO RATED INFO BASIC INFO ADVANCE SAVE SETTING Use...

Страница 17: ...the icon to enter control sub menu D ATALO G I N FO SETTI N G M EASU R E C O N TR O L H O M E 20KVA Bypass M ode 19 52 36 2018 11 07 O N O FF U PS BATT TEST M U TE ALL O N O FF C H AR G ER Touch icon...

Страница 18: ...trol sub menu D ATALO G I N FO SETTI N G M EASU R E C O N TR O L H O M E 20KVA Bypass M ode 19 52 36 2018 11 07 O N O FF U PS BATT TEST M U TE ALL O N O FF C H AR G ER Touch icon to return back to mai...

Страница 19: ...attery testing during battery test period After few seconds battery test result will show on the screen Touch Back to return to main screen immediately or No to cancel this operation and back to main...

Страница 20: ...L screen D ATALO G I N FO SETTI N G M EASU R E C O N TR O L H O M E 20KVA Bypass M ode 19 52 36 2018 11 07 O N O FF U PS BATT TEST M U TE ALL O N O FF C H AR G ER Tur n O n C har ger YES N O D ATALO G...

Страница 21: ...U S N VO L C H AR G C U R R D I SC H G C U R R TEM P R 125 0V 231 3V 229 5V 3 9A 0 0A 27 46VA 46VA 46VA 0 0 0 TO TAL VA O U TPU T W O U TPU T VA R S T 0 0 BATT N VO L TEM P S TEM P T 27 27 Measure scr...

Страница 22: ...back to previous menu NOTE Not all settings are available in every operation mode If the setting is not available in present mode the LCD will keep its original setting parameter showed instead of cha...

Страница 23: ...Xtreme Power Conversion Corporation E91 User s Manual Page 23 Uninterruptible Power Supply The authority list...

Страница 24: ...month and date are set Language Set the LCD language Only English is available Input Source Select the input source There are two options Line utility and generator Line is default setting This settin...

Страница 25: ...e can be done only in Line mode and ECO mode Enable UPS will transfer between line mode and eco mode as needed Disable UPS will remain in programmed mode Disable is the default setting ADVANCE D ATALO...

Страница 26: ...e two options 120V and 127V 120Vac is default setting Output Frequency Select output rated frequency 50Hz The output frequency is setting for 50Hz 60Hz The output frequency is setting for 60Hz 60Hz is...

Страница 27: ...ge range L Low voltage point for bypass The setting range is 96V 110V 96V is default setting H High voltage point for bypass The setting range is 130V 146V 146V is default setting Bypass FRE Range Set...

Страница 28: ...Shutdown Voltage setting Shutdown Voltage If battery voltage is lower than this point in battery mode UPS will automatically shut down The setting range is 10 0V 12 0V 10 7V is default setting The se...

Страница 29: ...N TR O L H O M E 20KVA Bypass M ode 19 52 36 2018 11 07 ELEC TR O N I C BATT M I SC ELLAN EO U S U PS SELFTEST Advance Maintainer Setting Menu Page2 To access the Advance Maintainer Setting menu page...

Страница 30: ...charge current is listed below One charger board There are four options 1A 2A 3A 4A 4A is default setting Two charger boards There are two options 4A and 8A 4A is default setting Three charger boards...

Страница 31: ...E CONTROL HOME 20KVA StanbyMode 19 52 36 2018 11 07 SYS PARAMETER INSTALL INFO VOL CALI CURR CALI 2018 1 SYS Install Date INITIAL BAT Install Date 2018 1 1 1 Install info Page SYS Install Date Set the...

Страница 32: ...tter it s pressing up or down key Press up key to increase 0 1 and press down key to decrease 0 1 Press OK key to confirm the modification Output VOL Output voltage calibration Each click is 0 1 no ma...

Страница 33: ...atter it s pressing up or down key Press up key to increase 0 1 and press down key to decrease 0 1 Press OK key to confirm the modification INITIAL DATALOG INFO SETTING MEASURE CONTROL HOME 20KVA Stan...

Страница 34: ...ial the Parameters YES NO INITIAL PARAMETERS Page PARAMETERS After pressing the confirmation window it will pop up as shown in above screen Touch YES to restore default value Touch Back or No to cance...

Страница 35: ...ear all setting value in EEPROM Touch Back or No to cancel this operation and back to INITIAL menu page Initial Touch PAGE TOUCH CALI After pressing the confirmation window it will pop up as shown in...

Страница 36: ...EC O VO L R ange EC O FR E R ange 146V 64 0H z 56 0H z 115V 125V 58H z 62H z U PS SELFTEST Electrical Setting Page 2 Bypass at UPS off Select the bypass status when manually turning off the UPS This...

Страница 37: ...in battery mode UPS will automatically shut down The setting range is 10 0V 12 0V 10 7V is default setting The setting is only available for long run model Battery Parameter Battery AH setting batter...

Страница 38: ...dvance screen and enter Maintainer password It will show UPS SELFTEST selection in the screen In the screen all tested items are shown unknown Simply click UPS SELFTEST button the UPS will start self...

Страница 39: ...I nst al l D at e PAR St at e PAR I D 2018 2018 Si ngl e 1 I nput Sour ce Al l M ut e M ode M ut e 01 Li ne D i sabl e D i sabl e 01 01 01 Basic Information Page2 SYS Install Date The date of system...

Страница 40: ...z 80V 96V EC O VO L R ange EC O FR E R ange 56 0H z 115V 58 0H z 156V 64 0H z 146V 64 0H z 125V 62 0H z Parameter Information Page 1 Parameter Information Line Voltage Range The acceptable line input...

Страница 41: ...R est or e D el ay 0m i n 0m i n Parameter Information Page 3 Charger Number The information of charger number Max Charge CURR The setting value of the maximum charging current Float VOL The setting v...

Страница 42: ...battery pack to ON position this step only necessary for long run model Then set the line input breaker to ON position At the same time the fan will start running and the UPS will start initializatio...

Страница 43: ...he UPS will enter fault status At this time if bypass is enabled the UPS will power to the load via bypass If bypass function is disabled or the input power is not within bypass acceptable range it wi...

Страница 44: ...in warning status 1 When LCD screen shows Fault Mode and the buzzer beeps once every second it indicates that there are problems for UPS operation Users can read the warning message s from DATA LOG m...

Страница 45: ...output voltage between two UPSs for the same phase to make sure the phase sequence is correct If these two voltage differences are near to zero that means all connections are met Otherwise please chec...

Страница 46: ...then turn off the system All UPSs will transfer to Bypass mode Remove all the maintenance bypass covers and set the maintenance switches from UPS to BPS position Turn off all the input breakers and ba...

Страница 47: ...mal None 17 Inverter R S output line to line short circuited None 67 Bypass O P short circuited None 18 Inverter S T output line to line short circuited None 68 Bypass O P line to line short circuited...

Страница 48: ...situations are dif ferent in parallel system 04 IP phase abnormal 33 Locked in bypass after overload 3 times in 30 minutes 05 Bypass phase abnormal 34 Converter current unbal anced 07 Over charge 3A C...

Страница 49: ...rom UPS out put first Then shut down the UPS and restart it Fault code is shown as 43 UPS is overload too long and be comes fault Then UPS shut down automatically Remove excess loads from UPS output a...

Страница 50: ...rom the batteries Verify that no voltage between the battery terminals and the ground is present before maintenance or repair In this product the battery circuit is not isolated from the input voltage...

Страница 51: ...9 x 26 3 x 32 3 11 9 x 34 x 40 2 23 6 x 31 1 x 65 4 Weight 315 lbs 504 lbs 510 lbs 690 lbs 831 lbs OPTIONAL BATTERY PACK Model EBP09 2 EBP09 5 EBP10 5 Battery quantity and size 40 12V 9AH 100 12V 9AH...

Страница 52: ...sk you for the above information and if possible help solve your problem over the phone In the event that the unit requires factory service the technician will issue you a Return Mate rial Authorizati...

Страница 53: ...approved third party b the equipment is damaged by the customer is improperly used or stored is subjected to an adverse operating environment or is operated outside the limits of its electrical specif...

Отзывы: