Xtreme Power Conversion Corporation
E91 User’s Manual
Page 27
Uninterruptible Power Supply
DATALOG
I NFO
SETTI NG
MEASURE
CONTROL
HOME
20KVA
Bypass Mode
19:52:36
2018-11-07
ELECTRONI C
BATTERY
MI SCELLANEOUS
Bypass UPS Of f
Bypass VOL Range
Bypass FRE Range
ECO Mode
96V
Enabl e
Di sabl e
ECO VOL Range
ECO FRE Range
146V
64. 0Hz
56. 0Hz
115V
125V
58Hz
62Hz
Electrical Setting Page 2
• Bypass at UPS off: Select the bypass status when manually turning off the UPS. This setting is only
available when “Bypass forbid.” is set to “Disable”.
Enable
: Bypass enabled. When selected, bypass mode is activated. Enable is the default setting.
Disable
: Bypass disabled. When selected, no output through bypass when manually turning off the
UPS.
• Bypass Voltage Range: Set the bypass voltage range.
L: Low voltage point for bypass. The setting range is 96V ~ 110V. 96V is default setting.
H: High voltage point for bypass. The setting range is 130V ~ 146V. 146V is default setting.
• Bypass FRE Range: Set the bypass frequency range.
• The acceptable bypass frequency range from 46Hz to 54Hz when UPS is 50Hz system and from 56Hz
to 64Hz when UPS is 60Hz system. 56Hz to 64Hz is the default setting.
• ECO mode: Enable/Disable ECO mode. Disable is the default setting.
• ECO Voltage Range: Set the ECO voltage range.
L: Low voltage point for ECO mode. The setting range is from “Rated output voltage – 5V” to “Rated
output voltage - 11V”. “Rated output voltage – 5V” is default setting.
H: High voltage point for ECO mode. The setting range is from “Rated output v 5V” to
“Rated output v 11V”. “Rated output v 5V” is default setting.
• ECO FRE Range: Set the ECO frequency range. The setting range is from 46Hz to 54Hz when the UPS
is 50Hz system and from 56Hz to 64Hz when the UPS is 60Hz system. 56Hz to 64Hz is the default