![Xtreme Power Conversion P91 Скачать руководство пользователя страница 27](http://html1.mh-extra.com/html/xtreme-power-conversion/p91/p91_service-manual_891029027.webp)
Xtreme Power Conversion Corporation
P91, TX91, TX91L, TXVR Service Manual
Page 27
Uninterruptible Power Supply
6k Main Power Section
Circuit Block
Checked components
Component Type
Failure condition
FUSE
F3,F4
Fuse
Open
Rectifier
Q17, Q18, Q21
SCR
A-K Short or open
PFC
D33, D35
Diode
Short or open
Q22, Q23
IGBT
C-E short or open
INV
D62, D52
Diode
Short or open
Q7, Q8, Q9, Q10
IGBT
C-E short or open
STS
Q1, Q2, Q3, Q4
SCR
A-K Short or open
SPS-Charger Section
Circuit Block
Checked components
Component Type
Failure condition
D2, D3, D7, D8, D11
Diode
Short or open
Q1, Q2
MOSFET
D-S short or open
IC1
Power IC
I-O short or open
Others
Q28
MOSFET
D-S short or open
F1
Fuse
Open
REC1
Rectifier Bridge
Short or open
Q6, Q15, Q28
MOSFET
D-S short or open
D8, D16, D13, D7, D17,
D18 ,D33
Power Diode
Short or open
U1, U4
Power IC
I-O short or open
U9, U10
Power Control IC
Vcc short to GND
Note: If the fuse is in “open” status, don’t replace the fuse only. In most of cases, open fuse is caused by other
failed components. Therefore, before restarting the UPS, you must find all failed components and replace them.