![Xtreme Power Conversion P91 Скачать руководство пользователя страница 22](http://html1.mh-extra.com/html/xtreme-power-conversion/p91/p91_service-manual_891029022.webp)
Xtreme Power Conversion Corporation
P91, TX91, TX91L, TXVR Service Manual
Page 22
Uninterruptible Power Supply
Warning code
Warning event
01
Battery unconnected
07
Over charge
08
Low battery
09
Overload
0A
Fan failure
0B
EPO enable
0D
Over temperature
0E
Charger failure
44
Failure on parallel redundancy
10
L1 IP fuse broken
21
Line situations are different in parallel system
22
Bypass situations are different in parallel system
33
Locked in bypass after overload 3 times in 30min
3A
Cover of maintain switch is open
3D
Bypass unstable
3E
Boot loader is missing
42
Over-temperature on transformer
45
Overload on parallel redundancy
Warning
Icon (flashing)
Alarm
Battery low
Beeping every second
Overload
Beeping twice every second
Battery unconnected
Beeping every second
Over charge
Beeping every second
EPO enable
Beeping every second
Fan failure/Over temperature
Beeping every second
Charger failure
Beeping every second
I/P fuse broken
Beeping every second
Overload 3 times in 30min
Beeping every second