NXRi-6KL, NXRi-10KL USER MANUAL
UNINTERRUPTIBLE POWER SUPPLY (UPS)
Xtreme Power Conversion® (XPC) Corporation (Rev 2/7/13)
Page 21
Step 6
Rail kit installation is now complete.
UPS Installation
Installation and wiring must be performed in accordance with the local electrical laws and regulations,
and performed by appropriate personnel.
1.
Make sure the utility wire and circuit breakers are rated per the capacity of the UPS to avoid
hazards of electrical shock or fire.
Note:
Do not use a wall receptacle as the input power for the UPS as its rated current is less
than the UPS maximum input current.
2.
Switch off the utility circuit breaker before installation.
3.
Turn off all connected devices before connecting to the UPS.
4.
Wiring sizes should be installed in accordance with the following table:
Model
Wiring specification (AWG)
INPUT
OUTPUT
BATTERY
GROUND
6KL
10
10
10
10
10KL
8
8
8
8
Note:
The cable for 6K should be able to withstand over 40A current. It is recommended to use
10AWG or thicker wire for safety and efficiency.
Note:
The cable for 10K should be able to withstand over 63A current. It is recommended to
use 10AWG or thicker wire for safety and efficiency.
Note:
The selections for color of wires should be in accordance with the local electrical laws
and regulations