NXRi-6KL, NXRi-10KL USER MANUAL
UNINTERRUPTIBLE POWER SUPPLY (UPS)
Xtreme Power Conversion® (XPC) Corporation (Rev 2/7/13)
Page 38
LCD Parameter Settings
There are three parameters to set up the UPS. Refer to the following diagram.
LCD PARAMETER DEFINITION
Parameter 1:
for program alternatives – there are 15 programs to set up – refer to the table below
Parameter 2 and 3:
are the setting options or values of each program
15 programs available list for parameter 1:
Code Description
Bypass
AC
ECO
CVCF Battery
Battery
Test
01
Output voltage
Y
02
Output frequency
Y
03
Voltage range for bypass
Y
04
Frequency range for bypass
Y
05
ECO mode enable/disable
Y
06
Voltage range for ECO mode
Y
07
ECO mode frequency range setting
Y
08
Bypass mode setting
Y
Y
09
Battery backup time setting
Y
Y
Y
Y
Y
Y
10
(not used for these models)
N/A
11
(not used for these models)
N/A
12
Hot standby function enable/disable
Y
Y
Y
Y
Y
Y
13
Battery voltage adjustment
Y
Y
Y
Y
Y
Y
14
Charger voltage adjustment
Y
Y
Y
Y
Y
Y
15
Output voltage adjustment
Y
Y
Y
*Y means that this program can be set in this mode.